Chapter 6 VAV AHU example<br />

Figure 107: Supply fan control<br />

Figure 108: Duct static pressure control<br />

Controlling the duct static pressure<br />

After starting the supply fan, modulate the supply fan speed to maintain<br />

the duct static pressure setpoint, 1.5 in. wg (adjustable). Use a PID loop,<br />

as shown in Figure 108.<br />

• Use a Network Configuration Input (nci) block to access the duct<br />

static pressure setpoint associated with the DAC profile.<br />

➤ Using the Network Configuration Input (nci) block<br />

Use a network configuration input (nci) in a program with this block.<br />

Select the specific nci in the properties dialog box.<br />

• In the duct static pressure control programming, set the PID loop<br />

properties as shown in Figure 109 on page 117.<br />