Writing the fan control program<br />

• Use the Occupancy and the De-Enumerator blocks to interpret the<br />

occupancy mode of the controller.<br />

➤ Using the Occupancy block<br />

Use the Occupancy block to provide a program with the occupancy<br />

state of the controller. The output of the Occupancy block is the result<br />

of arbitration among various schedule-related inputs and results in<br />

the appropriate enumerated value for the current occupancy state.<br />

Enumerations of the Occupancy block output are as follows:<br />

0 = Occupied<br />

1 = Unoccupied<br />

2 = Occupied bypass<br />

3 = Occupied standby<br />

For more information about the Occupancy block, see the <strong>Tracer</strong><br />

MP580/581 Programmable Controller <strong>Programming</strong> guide<br />

(CNT-SVP01A-EN).<br />

➤ Using the De-Enumerator block<br />

Use the De-Enumerator block to translate an analog enumeration to<br />

one of several possible binary output values. If the analog value input<br />

is equal to one of the enumerations for which the block tests, the<br />

appropriate binary output is set to true. All other binary outputs are<br />

set to false. Use the properties dialog box to select the configuration<br />

and specify the required outputs.<br />

• Use the binary variable, Manual Reset Alarm, to carry the alarm status<br />

associated with manual reset alarm conditions, including low<br />

mixed air temperature and high duct static pressure. If this alarm is<br />

active, it prevents the fan from starting.<br />

• Use the Feedback Alarm block to start the fan and confirm fan status.<br />

A fan failure occurs if status cannot be confirmed after a 1-minute<br />

delay.<br />

• Connect the actual Output Status block to the Feedback Alarm block.<br />

Use the output status to allow overrides of the fan without indicating<br />

afanfailure.<br />

CNT-APG001-EN 115