Applications Guide Tracer Graphical Programming - Trane

Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane

28.09.2014 Views

® Chapter 6 VAV AHU example control the outdoor air damper to its closed position. Also, if the supply fan is off or the status of the mixed air temperature sensor is failed, control the outdoor air damper to its closed position. Exhaust fan Coordinate exhaust fan operation with the unit supply fan and outdoor air damper position. Turn on the exhaust fan whenever the supply fan is on and the outdoor air damper is open beyond 30%. The exhaust fan remains on until the outdoor air damper closes to below 20% open or the supply fan is turned off. Cooling valve Modulate the cooling valve to maintain the discharge air temperature at the discharge air cooling setpoint. If the economizer function is enabled and the outdoor air damper is not open at least 90%, control the cooling valve to its closed position. Also, close the cooling valve if the air handler is in heat mode, the supply fan is off, or the discharge air temperature sensor is failed. Heating valve Modulatetheheatingvalvetomaintainthedischargeairtemperatureat the discharge air heating setpoint. Close the heating valve if the air handler is in cool mode, the supply fan is off, or the discharge air temperature sensor is failed. Open the heating valve if the supply fan is off and the outdoor air temperature falls below the adjustable freeze avoidance setpoint. Alarms In addition to the alarm requirements mentioned above, indicate an alarm at the operator display and turn on the alarm output when any sensor fails. Alarms must be resettable at the operator display. Diagnostic conditions include the following: • Dirty filter • Duct static pressure high limit • Exhaust fan failure • Low outdoor air temperature • Low (mixed air) temperature detection • Sensor failure (including discharge air temperature, mixed air temperature, outdoor air temperature, space temperature, and duct static pressure) • Supply fan failure The following failures shutdown the air handler and require a manual reset: • Discharge air or mixed air temperature sensor failure • Fan failure • High duct static pressure • Low mixed air temperature 108 CNT-APG001-EN

® Reviewing the sequence of operation Table 12: VAV AHU inputs and outputs data definition The corresponding data definition is presented in Table 12 on page 109 and Table 13 on page 110, and a wiring diagram is presented in Figure 105 on page 112. Inputs and outputs Type Name Notes Inputs 1 Analog Space Temp Universal input configured as thermistor or RTD 2 Analog Thumbwheel SP Universal input configured as thermistor or RTD 3 Analog Mixed Air Temp Universal input configured as thermistor or RTD 4 Analog Discharge Air Temp Universal input configured as thermistor or RTD 5 Analog Outdoor Air Temp Universal input configured as thermistor 6 — Not Used 7 Binary Low Temp Detect 8 Binary Run/Stop Interlock 9 Binary Occupancy/Generic 10 Binary Supply Fan Status 11 Binary Filter Status 12 Binary Exhaust Fan Status Pressure Duct Static Pressure There are no configurable properties for the pressure input. Binary outputs 1 Supply Fan Start/Stop 2 Exhaust Fan Start/Stop 3 Not Used 4 Not Used 5 Not Used 6 Alarm Output Status/custom alarm indicator Analog outputs 1 Supply Fan Speed Analog output configured as voltage, 0–10 V 2 Cooling Valve Position Analog output configured as voltage, 0–10 V 3 Heating Valve Position Analog output configured as voltage, 0–10 V 4 Face and Bypass Damper* Analog output configured as voltage, 0–10 V 5 OA Damper Position Analog output configured as voltage, 0–10 V 6 Not Used * This output is not used in this program but is often used in air-handler programs. Note: The inputs and outputs in this table are configured so that a Tracer AH540 main logic board could be replaced with a Tracer MP580/581 board, except for the Mixed Air Temp, which is input 6 on the Tracer AH540. CNT-APG001-EN 109

®<br />

Chapter 6 VAV AHU example<br />

control the outdoor air damper to its closed position. Also, if the supply<br />

fan is off or the status of the mixed air temperature sensor is failed, control<br />

the outdoor air damper to its closed position.<br />

Exhaust fan<br />

Coordinate exhaust fan operation with the unit supply fan and outdoor<br />

air damper position. Turn on the exhaust fan whenever the supply fan is<br />

on and the outdoor air damper is open beyond 30%. The exhaust fan<br />

remains on until the outdoor air damper closes to below 20% open or the<br />

supply fan is turned off.<br />

Cooling valve<br />

Modulate the cooling valve to maintain the discharge air temperature at<br />

the discharge air cooling setpoint. If the economizer function is enabled<br />

and the outdoor air damper is not open at least 90%, control the cooling<br />

valve to its closed position. Also, close the cooling valve if the air handler<br />

is in heat mode, the supply fan is off, or the discharge air temperature<br />

sensor is failed.<br />

Heating valve<br />

Modulatetheheatingvalvetomaintainthedischargeairtemperatureat<br />

the discharge air heating setpoint. Close the heating valve if the air handler<br />

is in cool mode, the supply fan is off, or the discharge air temperature<br />

sensor is failed. Open the heating valve if the supply fan is off and the<br />

outdoor air temperature falls below the adjustable freeze avoidance setpoint.<br />

Alarms<br />

In addition to the alarm requirements mentioned above, indicate an<br />

alarm at the operator display and turn on the alarm output when any<br />

sensor fails. Alarms must be resettable at the operator display. Diagnostic<br />

conditions include the following:<br />

• Dirty filter<br />

• Duct static pressure high limit<br />

• Exhaust fan failure<br />

• Low outdoor air temperature<br />

• Low (mixed air) temperature detection<br />

• Sensor failure (including discharge air temperature, mixed air temperature,<br />

outdoor air temperature, space temperature, and duct static<br />

pressure)<br />

• Supply fan failure<br />

The following failures shutdown the air handler and require a manual<br />

reset:<br />

• Discharge air or mixed air temperature sensor failure<br />

• Fan failure<br />

• High duct static pressure<br />

• Low mixed air temperature<br />

108 CNT-APG001-EN

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!