Reviewing the sequence of operation<br />

ture setpoint and the configured, default occupied and occupied standby<br />

setpoints.<br />

Note:<br />

Calculate the effective cooling and heating setpoints as in other<br />

Comm5 devices. See “Calculating the effective space setpoints”<br />

on page 135 for more information.<br />

Discharge air setpoints<br />

For discharge air control, use the configured, default discharge air temperature<br />

cooling and heating setpoints.<br />

Heat/Cool arbitration<br />

Determine the heat/cool decision of the air handler based on the effective<br />

occupied cooling and heating setpoints. Transition the air handler to cooling<br />

if the space temperature exceeds the cooling setpoint plus 1°F. Transition<br />

the air handler to heating if the space temperature falls below the<br />

heating setpoint minus 1°F.<br />

Control<br />

The following parameters for the sequence of operation are presented<br />

according to the equipment that must be controlled.<br />

Supply fan<br />

Operate the supply fan whenever the air handler is in occupied mode and<br />

modulate the fan speed to maintain the duct static pressure setpoint,<br />

1.5 in. wg (adjustable). Turn the supply fan off whenever one of the following<br />

occurs:<br />

• The air handler is unoccupied.<br />

• The run/stop interlock is open.<br />

• ThemixedairtemperatureistoocoldandtheLowTemperature<br />

Detection input is closed.<br />

• The supply fan status indicates a fan failure after a 1-minute delay.<br />

If the duct static pressure exceeds 4 in. wg, shut down the air handler<br />

immediately.<br />

Outdoor air damper<br />

When the economizer function is enabled and the outdoor air temperature<br />

is less than the economizer changeover setpoint, modulate the outdoor<br />

air damper between the adjustable minimum position and fully open<br />

to maintain the discharge air cooling setpoint. Modulate the outdoor air<br />

damper closed, overriding the minimum position, to maintain the mixed<br />

air temperature at or above the mixed air setpoint.<br />

If the economizer function is disabled, or the air handler is in the heat<br />

mode, control the outdoor air damper to its minimum position. If the outdoor<br />

air temperature falls below a low outdoor air temperature limit, control<br />

the outdoor air damper to its closed position. In unoccupied mode,<br />

CNT-APG001-EN 107