® Chapter 5 Cooling tower with variable-speed fan example Table 7: Cooling tower with variable-speed fan drive data definition (continued) Data Type Name Notes Outputs Analog Fan Speed Analog output configured as voltage, 2–10 V Binary Fan Start/Stop Apply sufficient minimum on/off timers to prevent excessive fan cycling. Sump Heater Apply sufficient minimum on/off timers to prevent excessive heater cycling. Pump Start/Stop Apply sufficient minimum on/off timers to prevent excessive pump cycling. Alarm Variables Analog Supply Temp Setpoint Sump Heater Setpoint Sump Alarm Setpoint Delta Temp Wet-Bulb Temp Approach Temp Analog variable, source set to operator display/service tool Analog variable, source set to operator display/service tool Analog variable, source set to operator display/service tool Analog variable, source set to program Analog variable, source set to program Analog variable, source set to program Binary Pump Fail Binary variable, source set to program Alarm Reset Binary variable, source set to operator display/service tool and program* * The binary variable, Alarm Reset, is sourced from both the operator display/service tool and the program. This allows the user to turn on the reset. After the alarm is reset, the program turns the Alarm Reset off. Before you start to write the program, configure these inputs, outputs, and variables in your Tracer MP580. Then open the TGP editor. 82 CNT-APG001-EN
® Reviewing the sequence of operation Figure 85: Cooling tower with variable-speed fan drive wiring diagram CNT-APG001-EN 83
- Page 56 and 57: ® Chapter 3 Modifying the exhaust
- Page 58 and 59: ® Chapter 3 Modifying the exhaust
- Page 60 and 61: ® Chapter 3 Modifying the exhaust
- Page 62 and 63: ® Chapter 3 Modifying the exhaust
- Page 64 and 65: ® Chapter 3 Modifying the exhaust
- Page 66 and 67: ® Chapter 3 Modifying the exhaust
- Page 68 and 69: ® Chapter 3 Modifying the exhaust
- Page 70 and 71: ® Chapter 3 Modifying the exhaust
- Page 72 and 73: ® Chapter 4 Cooling tower with two
- Page 74 and 75: ® Chapter 4 Cooling tower with two
- Page 76 and 77: ® Chapter 4 Cooling tower with two
- Page 78 and 79: ® Chapter 4 Cooling tower with two
- Page 80 and 81: ® Chapter 4 Cooling tower with two
- Page 82 and 83: ® Chapter 4 Cooling tower with two
- Page 84 and 85: ® Chapter 4 Cooling tower with two
- Page 86 and 87: ® Chapter 4 Cooling tower with two
- Page 88 and 89: ® Chapter 4 Cooling tower with two
- Page 90 and 91: ® Chapter 4 Cooling tower with two
- Page 92 and 93: ® Chapter 4 Cooling tower with two
- Page 94 and 95: ® Chapter 4 Cooling tower with two
- Page 96 and 97: ® Chapter 4 Cooling tower with two
- Page 98 and 99: ® Chapter 4 Cooling tower with two
- Page 100 and 101: ® Chapter 4 Cooling tower with two
- Page 102 and 103: ® Chapter 4 Cooling tower with two
- Page 104 and 105: ® Chapter 5 Cooling tower with var
- Page 108 and 109: ® Chapter 5 Cooling tower with var
- Page 110 and 111: ® Chapter 5 Cooling tower with var
- Page 112 and 113: ® Chapter 5 Cooling tower with var
- Page 114 and 115: ® Chapter 5 Cooling tower with var
- Page 116 and 117: ® Chapter 5 Cooling tower with var
- Page 118 and 119: ® Chapter 5 Cooling tower with var
- Page 120 and 121: ® Chapter 5 Cooling tower with var
- Page 122 and 123: ® Chapter 5 Cooling tower with var
- Page 124 and 125: ® Chapter 5 Cooling tower with var
- Page 126 and 127: ® Chapter 5 Cooling tower with var
- Page 128 and 129: ® Chapter 5 Cooling tower with var
- Page 130 and 131: ® Chapter 6 VAV AHU example Review
- Page 132 and 133: ® Chapter 6 VAV AHU example contro
- Page 134 and 135: ® Chapter 6 VAV AHU example Table
- Page 136 and 137: ® Chapter 6 VAV AHU example Figure
- Page 138 and 139: ® Chapter 6 VAV AHU example Figure
- Page 140 and 141: ® Chapter 6 VAV AHU example Figure
- Page 142 and 143: ® Chapter 6 VAV AHU example Figure
- Page 144 and 145: ® Chapter 6 VAV AHU example Figure
- Page 146 and 147: ® Chapter 6 VAV AHU example Figure
- Page 148 and 149: ® Chapter 6 VAV AHU example Figure
- Page 150 and 151: ® Chapter 6 VAV AHU example Figure
- Page 152 and 153: ® Chapter 6 VAV AHU example Writin
- Page 154 and 155: ® Chapter 6 VAV AHU example Indica
®<br />
Chapter 5 Cooling tower with variable-speed fan example<br />
Table 7: Cooling tower with variable-speed fan drive data definition (continued)<br />
Data Type Name Notes<br />
Outputs Analog Fan Speed Analog output configured as voltage, 2–10 V<br />
Binary Fan Start/Stop Apply sufficient minimum on/off timers to prevent<br />
excessive fan cycling.<br />
Sump Heater Apply sufficient minimum on/off timers to prevent<br />
excessive heater cycling.<br />
Pump Start/Stop Apply sufficient minimum on/off timers to prevent<br />
excessive pump cycling.<br />
Alarm<br />
Variables Analog Supply Temp<br />
Setpoint<br />
Sump Heater<br />
Setpoint<br />
Sump Alarm<br />
Setpoint<br />
Delta Temp<br />
Wet-Bulb Temp<br />
Approach Temp<br />
Analog variable, source set to operator display/service<br />
tool<br />
Analog variable, source set to operator display/service<br />
tool<br />
Analog variable, source set to operator display/service<br />
tool<br />
Analog variable, source set to program<br />
Analog variable, source set to program<br />
Analog variable, source set to program<br />
Binary Pump Fail Binary variable, source set to program<br />
Alarm Reset Binary variable, source set to operator display/service<br />
tool and program*<br />
* The binary variable, Alarm Reset, is sourced from both the operator display/service tool and the program. This allows the user<br />
to turn on the reset. After the alarm is reset, the program turns the Alarm Reset off.<br />
Before you start to write the program, configure these inputs, outputs,<br />
and variables in your <strong>Tracer</strong> MP580. Then open the TGP editor.<br />
82 CNT-APG001-EN