Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Chapter 5 Cooling tower with variable-speed fan example Reviewing the sequence of operation In this scenario a cooling tower with a variable-speed fan delivers condenser water to a small chiller plant. The following specifications apply to control of the cooling tower. Condenser water pump When condenser water is requested by the chiller plant, command the condenser water pump to start. If condenser water flow fails to be confirmed within 30 seconds, command the pump to stop and indicate a pump failure at the operator display and turn on the alarm output. A user must be able to reset the alarm at the operator display. Cooling tower fan Upon successful confirmation of condenser water flow, and when the cooling tower supply water temperature exceeds the setpoint by 2.5°F, turn on the fan. Modulate the fan to maintain the condenser water supply temperature according to setpoint. When the cooling tower supply water temperature is 2.5°F below the setpoint, turn off the fan. Note that the setpoint is adjustable from the operator display and that it is limited to a minimum of 65°F and a maximum of 95°F. Sump heater Cycle the sump heater if the sump temperature falls below 40°F (this value is adjustable at the operator display). If the outdoor air temperature falls below 32°F, turn on the sump heater continuously. If the sump temperature remains below 36°F (this value is adjustable at the operator display) for 15 minutes, or if the sump temperature falls below 32°F, indicate an alarm at the operator display and turn on the alarm output. Alarms In addition to the alarm requirements mentioned above, indicate an alarm at the operator display and turn on the alarm output when any sensor, including temperature and humidity, fails. Alarms must be resettable at the operator display. Calculations Calculate and display the change in water temperature across the cooling tower, the ambient wet-bulb temperature, and the approach temperature. (The approach temperature is defined as the difference between the ambient wet-bulb temperature and the condenser water supply temperature.) Thespecificationsforthepumpandthefanhavechanged.Thealarms have changed a little bit with the addition of the humidity sensor failure. The calculations section is completely new. 80 CNT-APG001-EN
® Reviewing the sequence of operation Analysis of this scenario results in Figure 84. The corresponding data definition is presented in Table 7, and a wiring diagram is presented in Figure 85 on page 83. Figure 84: Cooling tower with variable-speed fan drive data Table 7: Cooling tower with variable-speed fan drive data definition Data Type Name Notes Inputs Analog Supply Temp Universal input configured as thermistor or RTD (Balco, Platinum) Return Temp Universal input configured as thermistor or RTD (Balco, Platinum) Sump Temp Universal input configured as thermistor or RTD (Balco, Platinum) Binary Outdoor Air Temp Outdoor Air Humidity Flow Status Condenser Water Request Universal input configured as thermistor or RTD (Balco, Platinum) Universal input configured as a current input CNT-APG001-EN 81
- Page 54 and 55: ® Chapter 3 Modifying the exhaust
- Page 56 and 57: ® Chapter 3 Modifying the exhaust
- Page 58 and 59: ® Chapter 3 Modifying the exhaust
- Page 60 and 61: ® Chapter 3 Modifying the exhaust
- Page 62 and 63: ® Chapter 3 Modifying the exhaust
- Page 64 and 65: ® Chapter 3 Modifying the exhaust
- Page 66 and 67: ® Chapter 3 Modifying the exhaust
- Page 68 and 69: ® Chapter 3 Modifying the exhaust
- Page 70 and 71: ® Chapter 3 Modifying the exhaust
- Page 72 and 73: ® Chapter 4 Cooling tower with two
- Page 74 and 75: ® Chapter 4 Cooling tower with two
- Page 76 and 77: ® Chapter 4 Cooling tower with two
- Page 78 and 79: ® Chapter 4 Cooling tower with two
- Page 80 and 81: ® Chapter 4 Cooling tower with two
- Page 82 and 83: ® Chapter 4 Cooling tower with two
- Page 84 and 85: ® Chapter 4 Cooling tower with two
- Page 86 and 87: ® Chapter 4 Cooling tower with two
- Page 88 and 89: ® Chapter 4 Cooling tower with two
- Page 90 and 91: ® Chapter 4 Cooling tower with two
- Page 92 and 93: ® Chapter 4 Cooling tower with two
- Page 94 and 95: ® Chapter 4 Cooling tower with two
- Page 96 and 97: ® Chapter 4 Cooling tower with two
- Page 98 and 99: ® Chapter 4 Cooling tower with two
- Page 100 and 101: ® Chapter 4 Cooling tower with two
- Page 102 and 103: ® Chapter 4 Cooling tower with two
- Page 106 and 107: ® Chapter 5 Cooling tower with var
- Page 108 and 109: ® Chapter 5 Cooling tower with var
- Page 110 and 111: ® Chapter 5 Cooling tower with var
- Page 112 and 113: ® Chapter 5 Cooling tower with var
- Page 114 and 115: ® Chapter 5 Cooling tower with var
- Page 116 and 117: ® Chapter 5 Cooling tower with var
- Page 118 and 119: ® Chapter 5 Cooling tower with var
- Page 120 and 121: ® Chapter 5 Cooling tower with var
- Page 122 and 123: ® Chapter 5 Cooling tower with var
- Page 124 and 125: ® Chapter 5 Cooling tower with var
- Page 126 and 127: ® Chapter 5 Cooling tower with var
- Page 128 and 129: ® Chapter 5 Cooling tower with var
- Page 130 and 131: ® Chapter 6 VAV AHU example Review
- Page 132 and 133: ® Chapter 6 VAV AHU example contro
- Page 134 and 135: ® Chapter 6 VAV AHU example Table
- Page 136 and 137: ® Chapter 6 VAV AHU example Figure
- Page 138 and 139: ® Chapter 6 VAV AHU example Figure
- Page 140 and 141: ® Chapter 6 VAV AHU example Figure
- Page 142 and 143: ® Chapter 6 VAV AHU example Figure
- Page 144 and 145: ® Chapter 6 VAV AHU example Figure
- Page 146 and 147: ® Chapter 6 VAV AHU example Figure
- Page 148 and 149: ® Chapter 6 VAV AHU example Figure
- Page 150 and 151: ® Chapter 6 VAV AHU example Figure
- Page 152 and 153: ® Chapter 6 VAV AHU example Writin
®<br />
Reviewing the sequence of operation<br />
Analysis of this scenario results in Figure 84. The corresponding data definition<br />
is presented in Table 7, and a wiring diagram is presented in<br />
Figure 85 on page 83.<br />
Figure 84: Cooling tower with variable-speed fan drive data<br />
Table 7: Cooling tower with variable-speed fan drive data definition<br />
Data Type Name Notes<br />
Inputs Analog Supply Temp Universal input configured as thermistor or RTD<br />
(Balco, Platinum)<br />
Return Temp Universal input configured as thermistor or RTD<br />
(Balco, Platinum)<br />
Sump Temp Universal input configured as thermistor or RTD<br />
(Balco, Platinum)<br />
Binary<br />
Outdoor Air<br />
Temp<br />
Outdoor Air<br />
Humidity<br />
Flow Status<br />
Condenser<br />
Water Request<br />
Universal input configured as thermistor or RTD<br />
(Balco, Platinum)<br />
Universal input configured as a current input<br />
CNT-APG001-EN 81