28.09.2014 Views

12½ - 20 Tons - Trane

12½ - 20 Tons - Trane

12½ - 20 Tons - Trane

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Mechanical<br />

Specifications<br />

Additional Factory Installed<br />

Options (FIOPS)<br />

Electric Heaters<br />

Factory installed and wired electric<br />

heaters are available for all 3 phase<br />

horizontal and downflow <strong>12½</strong> - <strong>20</strong> tons. If<br />

ordering the Through the Base Electrical<br />

option with an Electric Heater, the heater<br />

must be factory installed.<br />

Through the Base Electrical with Circuit<br />

Breaker<br />

This option is a factory installed thermal<br />

magnetic, molded case, HACR Circuit<br />

Breaker with provisions for through the<br />

base electrical connections. The circuit<br />

breaker will be installed in a water tight<br />

enclosure in the unit with access through<br />

a swinging door. Factory wiring will be<br />

provided from the switch to the unit high<br />

voltage terminal block. The circuit<br />

breaker will provide overcurrent<br />

protection, be sized per NEC and UL<br />

guidelines, and be agency recognized by<br />

UL/CSA. This option is available on all<br />

<strong>12½</strong>-<strong>20</strong> tons downflow models.<br />

Powered or Unpowered Convenience<br />

Outlet<br />

This option is a GFCI, 1<strong>20</strong>v/15amp, 2<br />

plug, convenience outlet, either powered<br />

or unpowered. When the convenience<br />

outlet is powered, a service receptacle<br />

disconnect will be available. The<br />

convenience outlet is powered from the<br />

line side of the disconnect or circuit<br />

breaker, and therefore will not be<br />

affected by the position of the disconnect<br />

or circuit breaker. This option can only be<br />

ordered when the Through the Base<br />

Electrical with either the Disconnect<br />

Switch, or Circuit Breaker, option is<br />

ordered. This option is available on all<br />

<strong>12½</strong>-<strong>20</strong> tons downflow models.<br />

Clogged Filter/Fan Failure Switch<br />

A dedicated differential pressure switch<br />

is available to achieve active fan failure<br />

indication and/or clogged filter<br />

indication. These indications will be<br />

registered with either a zone sensor with<br />

status indication lights or an Integrated<br />

Comfort System.<br />

Reference or Comparative Enthalpy<br />

Reference or Comparative Enthalpy<br />

option shall be available when a factory<br />

installed Downflow Economizer is<br />

ordered. This option is available on all<br />

<strong>12½</strong>-<strong>20</strong> tons downflow models.<br />

High Pressure Cutout<br />

This option is offered for units that do<br />

not have High Pressure cutout as<br />

standard. The Voyager units with High<br />

Pressure Cutout as standard are<br />

WC*180-240B.<br />

Hinged Access Doors<br />

Sheet metal hinges are available factory<br />

installed on the Filter/Evaporator Access<br />

Door and the Compressor/Control<br />

Access Door. This option is available on<br />

all <strong>12½</strong>-<strong>20</strong> tons downflow models.<br />

<strong>Trane</strong> Communications Interface (TCI)<br />

An option for a factory installed <strong>Trane</strong><br />

Communication Interface is available to<br />

allow twisted wire pair communication<br />

with an Integrated Comfort System.<br />

Order this option when a combination of<br />

TCI and oversized motor is desired.<br />

Discharge Air Sensing Kit<br />

This kit provides true discharge air<br />

sensing in heating models. This sensor is<br />

a status indicator readable through<br />

Tracer or Tracker. The kit is functional<br />

only with the ReliaTel Options Module.<br />

Coil Guards<br />

Hail protection quality coil guards shall be<br />

either factory or field-installed for<br />

condenser coil protection.<br />

High Efficiency Motors<br />

This option is available with efficiency<br />

ratings from 86.5 up to 91.0. It is not<br />

available for all models.<br />

50 PKGP-PRC001-EN