Electrical Data Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued) Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or Tons With Model No. KW Rating 1 Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker 2 12½ 15 20 575 Volts Three Phase AYDHTRKW18A 18.0 1 47 50 49 50 WCD150BW AYDHTRKW36A 36.0 2 69 70 71 80 AYDHTRKW54A 54.0 2 90 90 93 100 AYHHTRNW18A 18.0 1 47 50 49 50 WCH150BW AYHHTRQW36A 36.0 2 69 70 71 80 AYHHTRPW54A 54.0 2 90 90 93 100 AYDHTRKW18A 18.0 1 54 60 56 60 WCD180BW AYDHTRKW36A 36.0 2 76 80 78 80 AYDHTRKW54A 54.0 2 97 100 99 100 AYHHTRNW18A 18.0 1 54 60 56 60 WCH180BW AYHHTRQW36A 36.0 2 76 80 78 80 AYHHTRPW54A 54.0 2 97 100 99 100 AYDHTRLW36A 36.0 2 81 90 84 90 WCD240BW AYDHTRLW54A 54.0 2 103 110 106 110 AYDHTRKW72A 72.0 2 125 125 128 150 AYHHTRNW36A 36.0 2 81 90 84 90 WCH240BW AYHHTRNW54A 54.0 2 103 110 106 110 AYHHTRNW72A 72.0 2 125 125 128 150 NOTES: 1. Heater kw ratings are at 600V for 575V unit 2. HACR type circuit breaker per NEC. *Indicates both downflow and horizontal units. 30 PKGP-PRC001-EN

Electrical Data Table ED-4 — Electrical Characteristics — Evaporator Fan Motors — 60 Cycle Standard Evaporator Fan Motor Oversized Evaporator Fan Motor Amps Amps Unit Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA WC*150B3 1 208-230 3 3.00 10.6 81.0 1 208-230 3 5.00 16.7 109.8 12½ WC*150B4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9 WC*150BW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6 WC*180B3 1 208-230 3 3.00 10.6 81.0 1 208-230 3 5.00 16.7 109.8 15 WC*180B4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9 WC*180BW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6 WC*240B3 1 208-230 3 5.00 16.7 109.8 1 208-230 3 7.50 17.6 120.4 20 WC*240B4 1 460 3 5.00 7.6 54.9 1 460 3 7.50 8.6 74.0 WC*240BW 1 575 3 5.00 6.1 41.6 1 575 3 7.50 7.0 60.0 *Indicates both downflow and horizontal units. PKGP-PRC001-EN 31

Electrical<br />

Data<br />

Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued)<br />

Standard Indoor Motor<br />

Oversize Indoor Motor<br />

To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or<br />

<strong>Tons</strong> With Model No. KW Rating 1 Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker 2<br />

<strong>12½</strong><br />

15<br />

<strong>20</strong><br />

575 Volts Three Phase<br />

AYDHTRKW18A 18.0 1 47 50 49 50<br />

WCD150BW AYDHTRKW36A 36.0 2 69 70 71 80<br />

AYDHTRKW54A 54.0 2 90 90 93 100<br />

AYHHTRNW18A 18.0 1 47 50 49 50<br />

WCH150BW AYHHTRQW36A 36.0 2 69 70 71 80<br />

AYHHTRPW54A 54.0 2 90 90 93 100<br />

AYDHTRKW18A 18.0 1 54 60 56 60<br />

WCD180BW AYDHTRKW36A 36.0 2 76 80 78 80<br />

AYDHTRKW54A 54.0 2 97 100 99 100<br />

AYHHTRNW18A 18.0 1 54 60 56 60<br />

WCH180BW AYHHTRQW36A 36.0 2 76 80 78 80<br />

AYHHTRPW54A 54.0 2 97 100 99 100<br />

AYDHTRLW36A 36.0 2 81 90 84 90<br />

WCD240BW AYDHTRLW54A 54.0 2 103 110 106 110<br />

AYDHTRKW72A 72.0 2 125 125 128 150<br />

AYHHTRNW36A 36.0 2 81 90 84 90<br />

WCH240BW AYHHTRNW54A 54.0 2 103 110 106 110<br />

AYHHTRNW72A 72.0 2 125 125 128 150<br />

NOTES:<br />

1. Heater kw ratings are at 600V for 575V unit<br />

2. HACR type circuit breaker per NEC.<br />

*Indicates both downflow and horizontal units.<br />

30 PKGP-PRC001-EN