Electrical<br />

Data<br />

Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued)<br />

Standard Indoor Motor<br />

Oversize Indoor Motor<br />

To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or<br />

<strong>Tons</strong> With Model No. KW Rating 1 Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker 2<br />

<strong>12½</strong><br />

15<br />

<strong>20</strong><br />

460 Volts Three Phase<br />

AYDHTRK418A 18.0 1 58 60 61 70<br />

WCD150B4 AYDHTRK436A 36.0 2 85 90 88 90<br />

AYDHTRK454A 54.0 2 112 125 115 125<br />

AYHHTRP418A 18.0 1 58 60 61 70<br />

WCH150B4 AYHHTRP436A 36.0 2 85 90 88 90<br />

AYHHTRP454A 54.0 2 112 125 115 125<br />

AYDHTRK418A 18.0 1 67 70 70 70<br />

WCD180B4 AYDHTRK436A 36.0 2 94 100 97 100<br />

AYDHTRK454A 54.0 2 121 125 124 125<br />

AYHHTRP418A 18.0 1 67 70 70 70<br />

WCH180B4 AYHHTRP436A 36.0 2 94 90 97 100<br />

AYHHTRP454A 54.0 2 121 125 124 125<br />

AYDHTRL436A 36.0 2 104 110 107 110<br />

WCD240B4 AYDHTRL454A 54.0 2 131 150 134 150<br />

AYDHTRK472A 72.0 2 158 175 161 175<br />

AYHHTRN436A 36.0 2 104 110 107 110<br />

WCH240B4 AYHHTRN454A 54.0 2 131 150 134 150<br />

AYHHTRN472A 72.0 2 158 175 161 175<br />

NOTES:<br />

1. Heater kw ratings are at 480V for 460V unit<br />

2. HACR type circuit breaker per NEC.<br />

PKGP-PRC001-EN 29