Electrical Data Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued) Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or Tons With Model No. KW Rating 1 Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker 2 12½ 15 20 208/230 Volts Three Phase AYDHTRK318A 13.5/18.0 1 113/120 125/125 119/127 125/150 WCD150B3 AYDHTRK336A 27.0/36.0 2 160/175 175/175 166/181 175/200 AYDHTRK354A 40.5/54.0 2 207/229 225/250 213/235 225/250 AYHHTRN318A 13.5/18.0 1 113/120 125/125 119/127 125/150 WCH150B3 AYHHTRP336A 27.0/36.0 2 160/175 175/175 166/181 175/200 AYHHTRP354A 40.5/54.0 2 207/229 225/250 213/235 225/250 AYDHTRK318A 13.5/18.0 1 124/131 125/150 130/137 150/150 WCD180B3 AYDHTRK336A 27.0/36.0 2 171/185 175/200 177/191 200/200 AYDHTRK354A 40.5/54.0 2 218/240 225/250 224/246 225/250 AYHHTRN318A 13.5/18.0 1 124/131 125/150 130/137 150/150 WCH180B3 AYHHTRP336A 27.0/36.0 2 171/185 175/200 177/191 200/200 AYHHTRP354A 40.5/54.0 2 218/240 225/250 224/246 225/250 AYDHTRL336A 27.0/36.0 2 190/204 200/225 197/212 200/225 WCD240B3 AYDHTRL354A 40.5/54.0 2 237/258 250/300 244/266 250/300 AYDHTRK372A 54.0/72.0 2 284/312 300/350 291/320 300/350 AYHHTRN336A 27.0/36.0 2 190/204 200/225 197/212 200/225 WCH240B3 AYHHTRN354A 40.5/54.0 2 237/258 250/300 177/266 250/300 AYHHTRN372A 54.0/72.0 2 284/312 300/350 224/320 300/350 NOTES: 1. Heater kw ratings are at 208/240 for 208/230V unit 480V for 460 V unit 2. HACR type circuit breaker per NEC. *Indicates both downflow and horizontal units. 28 PKGP-PRC001-EN

Electrical Data Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued) Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or Tons With Model No. KW Rating 1 Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker 2 12½ 15 20 460 Volts Three Phase AYDHTRK418A 18.0 1 58 60 61 70 WCD150B4 AYDHTRK436A 36.0 2 85 90 88 90 AYDHTRK454A 54.0 2 112 125 115 125 AYHHTRP418A 18.0 1 58 60 61 70 WCH150B4 AYHHTRP436A 36.0 2 85 90 88 90 AYHHTRP454A 54.0 2 112 125 115 125 AYDHTRK418A 18.0 1 67 70 70 70 WCD180B4 AYDHTRK436A 36.0 2 94 100 97 100 AYDHTRK454A 54.0 2 121 125 124 125 AYHHTRP418A 18.0 1 67 70 70 70 WCH180B4 AYHHTRP436A 36.0 2 94 90 97 100 AYHHTRP454A 54.0 2 121 125 124 125 AYDHTRL436A 36.0 2 104 110 107 110 WCD240B4 AYDHTRL454A 54.0 2 131 150 134 150 AYDHTRK472A 72.0 2 158 175 161 175 AYHHTRN436A 36.0 2 104 110 107 110 WCH240B4 AYHHTRN454A 54.0 2 131 150 134 150 AYHHTRN472A 72.0 2 158 175 161 175 NOTES: 1. Heater kw ratings are at 480V for 460V unit 2. HACR type circuit breaker per NEC. PKGP-PRC001-EN 29

Electrical<br />

Data<br />

Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued)<br />

Standard Indoor Motor<br />

Oversize Indoor Motor<br />

To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or<br />

<strong>Tons</strong> With Model No. KW Rating 1 Stages MCA Max Circuit Breaker 2 MCA Max Circuit Breaker 2<br />

<strong>12½</strong><br />

15<br />

<strong>20</strong><br />

<strong>20</strong>8/230 Volts Three Phase<br />

AYDHTRK318A 13.5/18.0 1 113/1<strong>20</strong> 125/125 119/127 125/150<br />

WCD150B3 AYDHTRK336A 27.0/36.0 2 160/175 175/175 166/181 175/<strong>20</strong>0<br />

AYDHTRK354A 40.5/54.0 2 <strong>20</strong>7/229 225/250 213/235 225/250<br />

AYHHTRN318A 13.5/18.0 1 113/1<strong>20</strong> 125/125 119/127 125/150<br />

WCH150B3 AYHHTRP336A 27.0/36.0 2 160/175 175/175 166/181 175/<strong>20</strong>0<br />

AYHHTRP354A 40.5/54.0 2 <strong>20</strong>7/229 225/250 213/235 225/250<br />

AYDHTRK318A 13.5/18.0 1 124/131 125/150 130/137 150/150<br />

WCD180B3 AYDHTRK336A 27.0/36.0 2 171/185 175/<strong>20</strong>0 177/191 <strong>20</strong>0/<strong>20</strong>0<br />

AYDHTRK354A 40.5/54.0 2 218/240 225/250 224/246 225/250<br />

AYHHTRN318A 13.5/18.0 1 124/131 125/150 130/137 150/150<br />

WCH180B3 AYHHTRP336A 27.0/36.0 2 171/185 175/<strong>20</strong>0 177/191 <strong>20</strong>0/<strong>20</strong>0<br />

AYHHTRP354A 40.5/54.0 2 218/240 225/250 224/246 225/250<br />

AYDHTRL336A 27.0/36.0 2 190/<strong>20</strong>4 <strong>20</strong>0/225 197/212 <strong>20</strong>0/225<br />

WCD240B3 AYDHTRL354A 40.5/54.0 2 237/258 250/300 244/266 250/300<br />

AYDHTRK372A 54.0/72.0 2 284/312 300/350 291/3<strong>20</strong> 300/350<br />

AYHHTRN336A 27.0/36.0 2 190/<strong>20</strong>4 <strong>20</strong>0/225 197/212 <strong>20</strong>0/225<br />

WCH240B3 AYHHTRN354A 40.5/54.0 2 237/258 250/300 177/266 250/300<br />

AYHHTRN372A 54.0/72.0 2 284/312 300/350 224/3<strong>20</strong> 300/350<br />

NOTES:<br />

1. Heater kw ratings are at <strong>20</strong>8/240 for <strong>20</strong>8/230V unit<br />

480V for 460 V unit<br />

2. HACR type circuit breaker per NEC.<br />

*Indicates both downflow and horizontal units.<br />

28 PKGP-PRC001-EN