Electrical<br />

Data<br />

Table ED-1 — Unit Wiring<br />

Standard Indoor Fan Motor<br />

Oversize Indoor Fan Motor<br />

Unit Minimum Maximum Fuse Size Minimum Maximum Fuse Size<br />

Unit Operating Circuit or Maximum Circuit or Maximum<br />

<strong>Tons</strong> Model No. Voltage Range Ampacity Circuit Breaker 1 Ampacity Circuit Breaker 1<br />

WC*150B3 187-253 66.0 80 72.0 80<br />

<strong>12½</strong> WC*150B4 414-506 31.0 40 34.0 40<br />

WC*150BW 517-633 25.0 30 28.0 35<br />

WC*180B3 187-253 77.0 90 83.0 100<br />

15 WC*180B4 414-506 40.0 45 43.0 50<br />

WC*180BW 517-633 32.0 35 34.0 40<br />

WC*240B3 187-253 96.0 125 103.0 125<br />

<strong>20</strong> WC*240B4 414-506 49.0 60 53.0 60<br />

WC*240BW 517-633 38.0 45 41.0 50<br />

NOTE:<br />

1. HACR type circuit breaker per NEC.<br />

Table ED-2 — Electrical Characteristics — Power Exhaust Accessory<br />

Accessory<br />

Amps<br />

Accessory<br />

Operating<br />

<strong>Tons</strong> Model Number Voltage Phase HP RPM FLA LRA<br />

<strong>12½</strong>, 15, <strong>20</strong><br />

BAYPWRX019 <strong>20</strong>8-230 1 3/4 1040 6.6 13.5<br />

BAYPWRX0<strong>20</strong> 460 1 3/4 1040 3.2 8.4<br />

BAYPWRX021 575 1 3/4 1040 2.1 5.2<br />

*Indicates both downflow and horizontal units.<br />