Performance Data (12½ - 20 Tons) Table PD-18— Heating Capacity Correction Factors % Variation of Nominal CFM - 20 - 10 0 + 10 + 20 Total Gross Capacity Multiplier .96 .98 1.0 1.01 1.02 Table PD-19 — Auxiliary Electric Heat Capacity Total 2 Stage 1 Stage 2 Unit KW MBh No. of KW MBh KW MBh Tons Model No. Input 1 Output 1 Stages Input 1 Output 1 Input 1 Output 1 18.00 61.00 1 18.00 61.00 — — 12½, 15 WC*150B3, B4, BW 36.00 123.00 2 18.00 61.00 18.00 61.00 WC*180B3, B4, BW 54.00 184.00 2 36.00 123.00 18.00 61.00 36.00 123.00 2 18.00 61.00 18.00 61.00 20 WC* 240B3, B4, BW 54.00 184.00 2 36.00 123.00 18.00 61.00 72.00 246.00 2 36.00 123.00 36.00 123.00 NOTES: 1. Does not include indoor fan power or heat. 2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =( Voltage ) 2 x rated cap. Rated Voltage Table PD-20 —Electric Heater Voltage Correction Factors (Applicable to Auxiliary Heat Capacity) Nominal Distribution Capacity Voltage Voltage Multiplier 208 0.75 240 230 0.92 240 1.00 440 0.84 480 460 0.94 480 1.00 540 0.81 600 575 0.92 600 1.00 *Indicates both downflow and horizontal units. 24 PKGP-PRC001-EN

Performance Data (12½ - 20 Tons) Table PD-21— Air Temperature Rise Across Electric Heaters (Degree F) 12½ Ton 15 Ton 20 Ton 5000 CFM 6000 CFM 8000 CFM Three Phase Three Phase Three Phase KW Stages WC*150B WC*180B WC*240B 9.00 1 — — — 17.30 1 — — — 18.00 1 11.4 9.5 — 27.00 2 — — — 36.00 2 23.0 19.0 14.2 54.00 2 34.1 28.4 21.3 72.00 2 — — 28.5 Table PD-22 — Electric Heater Temperature Rise Correction Factors % Variation From Nominal CFM - 20 - 15 - 10 - 5 0 +5 +10 +15 +20 Temperature Rise Multiplier 1.25 1.17 1.11 1.05 1.00 0.95 0.91 0.87 0.83 PKGP-PRC001-EN 25

Performance<br />

Data<br />

(<strong>12½</strong> - <strong>20</strong> <strong>Tons</strong>)<br />

Table PD-18— Heating Capacity Correction Factors<br />

% Variation of Nominal CFM - <strong>20</strong> - 10 0 + 10 + <strong>20</strong><br />

Total Gross Capacity Multiplier .96 .98 1.0 1.01 1.02<br />

Table PD-19 — Auxiliary Electric Heat Capacity<br />

Total 2 Stage 1 Stage 2<br />

Unit KW MBh No. of KW MBh KW MBh<br />

<strong>Tons</strong> Model No. Input 1 Output 1 Stages Input 1 Output 1 Input 1 Output 1<br />

18.00 61.00 1 18.00 61.00 — —<br />

<strong>12½</strong>, 15 WC*150B3, B4, BW 36.00 123.00 2 18.00 61.00 18.00 61.00<br />

WC*180B3, B4, BW 54.00 184.00 2 36.00 123.00 18.00 61.00<br />

36.00 123.00 2 18.00 61.00 18.00 61.00<br />

<strong>20</strong> WC* 240B3, B4, BW 54.00 184.00 2 36.00 123.00 18.00 61.00<br />

72.00 246.00 2 36.00 123.00 36.00 123.00<br />

NOTES:<br />

1. Does not include indoor fan power or heat.<br />

2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =( Voltage ) 2 x rated cap.<br />

Rated Voltage<br />

Table PD-<strong>20</strong> —Electric Heater Voltage<br />

Correction Factors (Applicable to Auxiliary<br />

Heat Capacity)<br />

Nominal Distribution Capacity<br />

Voltage Voltage Multiplier<br />

<strong>20</strong>8 0.75<br />

240 230 0.92<br />

240 1.00<br />

440 0.84<br />

480 460 0.94<br />

480 1.00<br />

540 0.81<br />

600 575 0.92<br />

600 1.00<br />

*Indicates both downflow and horizontal units.<br />

24 PKGP-PRC001-EN