Performance Data (12½ - 20 Tons) Table PD-18— Heating Capacity Correction Factors % Variation of Nominal CFM - 20 - 10 0 + 10 + 20 Total Gross Capacity Multiplier .96 .98 1.0 1.01 1.02 Table PD-19 — Auxiliary Electric Heat Capacity Total 2 Stage 1 Stage 2 Unit KW MBh No. of KW MBh KW MBh Tons Model No. Input 1 Output 1 Stages Input 1 Output 1 Input 1 Output 1 18.00 61.00 1 18.00 61.00 — — 12½, 15 WC*150B3, B4, BW 36.00 123.00 2 18.00 61.00 18.00 61.00 WC*180B3, B4, BW 54.00 184.00 2 36.00 123.00 18.00 61.00 36.00 123.00 2 18.00 61.00 18.00 61.00 20 WC* 240B3, B4, BW 54.00 184.00 2 36.00 123.00 18.00 61.00 72.00 246.00 2 36.00 123.00 36.00 123.00 NOTES: 1. Does not include indoor fan power or heat. 2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =( Voltage ) 2 x rated cap. Rated Voltage Table PD-20 —Electric Heater Voltage Correction Factors (Applicable to Auxiliary Heat Capacity) Nominal Distribution Capacity Voltage Voltage Multiplier 208 0.75 240 230 0.92 240 1.00 440 0.84 480 460 0.94 480 1.00 540 0.81 600 575 0.92 600 1.00 *Indicates both downflow and horizontal units. 24 PKGP-PRC001-EN
Performance Data (12½ - 20 Tons) Table PD-21— Air Temperature Rise Across Electric Heaters (Degree F) 12½ Ton 15 Ton 20 Ton 5000 CFM 6000 CFM 8000 CFM Three Phase Three Phase Three Phase KW Stages WC*150B WC*180B WC*240B 9.00 1 — — — 17.30 1 — — — 18.00 1 11.4 9.5 — 27.00 2 — — — 36.00 2 23.0 19.0 14.2 54.00 2 34.1 28.4 21.3 72.00 2 — — 28.5 Table PD-22 — Electric Heater Temperature Rise Correction Factors % Variation From Nominal CFM - 20 - 15 - 10 - 5 0 +5 +10 +15 +20 Temperature Rise Multiplier 1.25 1.17 1.11 1.05 1.00 0.95 0.91 0.87 0.83 PKGP-PRC001-EN 25
- Page 1 and 2: Packaged Heat Pumps Voyager 12½ -
- Page 3 and 4: Contents Introduction Features and
- Page 5 and 6: Features and Benefits ReliaTel Seve
- Page 7 and 8: Features and Benefits Capacity Modu
- Page 9 and 10: Selection Procedure Example: Coolin
- Page 11 and 12: General Data (12½ Ton) Table GD-1
- Page 13 and 14: Performance Data (12½ Ton) Table P
- Page 15 and 16: Performance Data (20 Ton) Table PD-
- Page 17 and 18: Performance Data (15 Ton) Table PD-
- Page 19 and 20: Performance Data (12½ - 20 Tons) T
- Page 21 and 22: Performance Data (12½ Ton) Table P
- Page 23: Performance Data (20 Ton) Table PD-
- Page 27 and 28: Electrical Data Table ED-1 — Unit
- Page 29 and 30: Electrical Data Table ED-3 — Unit
- Page 31 and 32: Electrical Data Table ED-4 — Elec
- Page 33 and 34: Jobsite Connections ZONE SENSORS DI
- Page 35 and 36: Typical Wiring (12½ - 20 Tons) PKG
- Page 37 and 38: Typical Wiring (12½ - 20 Tons) PKG
- Page 39 and 40: Dimensional Data (12½, 15 Ton) All
- Page 41 and 42: Dimensional Data (20 Ton) All dimen
- Page 43 and 44: Dimensional Data Factory Installed
- Page 45 and 46: Dimensional Data (12½ - 20 Tons) T
- Page 47 and 48: Weights 1 Table W- 2 — Maximum Un
- Page 49 and 50: Mechanical Specifications Accessori
- Page 51 and 52: Mechanical Specifications Supply an
Performance<br />
Data<br />
(<strong>12½</strong> - <strong>20</strong> <strong>Tons</strong>)<br />
Table PD-18— Heating Capacity Correction Factors<br />
% Variation of Nominal CFM - <strong>20</strong> - 10 0 + 10 + <strong>20</strong><br />
Total Gross Capacity Multiplier .96 .98 1.0 1.01 1.02<br />
Table PD-19 — Auxiliary Electric Heat Capacity<br />
Total 2 Stage 1 Stage 2<br />
Unit KW MBh No. of KW MBh KW MBh<br />
<strong>Tons</strong> Model No. Input 1 Output 1 Stages Input 1 Output 1 Input 1 Output 1<br />
18.00 61.00 1 18.00 61.00 — —<br />
<strong>12½</strong>, 15 WC*150B3, B4, BW 36.00 123.00 2 18.00 61.00 18.00 61.00<br />
WC*180B3, B4, BW 54.00 184.00 2 36.00 123.00 18.00 61.00<br />
36.00 123.00 2 18.00 61.00 18.00 61.00<br />
<strong>20</strong> WC* 240B3, B4, BW 54.00 184.00 2 36.00 123.00 18.00 61.00<br />
72.00 246.00 2 36.00 123.00 36.00 123.00<br />
NOTES:<br />
1. Does not include indoor fan power or heat.<br />
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =( Voltage ) 2 x rated cap.<br />
Rated Voltage<br />
Table PD-<strong>20</strong> —Electric Heater Voltage<br />
Correction Factors (Applicable to Auxiliary<br />
Heat Capacity)<br />
Nominal Distribution Capacity<br />
Voltage Voltage Multiplier<br />
<strong>20</strong>8 0.75<br />
240 230 0.92<br />
240 1.00<br />
440 0.84<br />
480 460 0.94<br />
480 1.00<br />
540 0.81<br />
600 575 0.92<br />
600 1.00<br />
*Indicates both downflow and horizontal units.<br />
24 PKGP-PRC001-EN