Performance<br />

Data<br />

(<strong>12½</strong> Ton)<br />

Table PD-6 — Evaporator Fan Performance — <strong>12½</strong> Ton — WC*150B<br />

External Static Pressure (Inches of Water)<br />

.10 .<strong>20</strong> .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive<br />

4000 — — 506 0.69 537 0.80 568 0.92 599 1.03 631 1.15 662 1.26 694 1.37 726 1.48 756 1.59<br />

4500 511 0.87 541 0.98 572 1.09 603 1.21 634 1.32 664 1.43 693 1.55 721 1.68 749 1.81 777 1.94<br />

5000 551 1.16 580 1.31 612 1.39 640 1.51 672 1.67 700 1.78 727 1.90 754 2.03 779 2.18 805 2.32<br />

5500 597 1.54 626 1.68 656 1.80 682 1.89 709 2.04 738 2.22 763 2.34 788 2.46 813 2.60 837 2.76<br />

6000 644 1.99 674 2.10 699 2.28 727 2.37 749 2.48 774 2.66 801 2.85 825 3.00 848 3.13 871 3.27<br />

3 HP Standard Motor & High<br />

Static Drive Accessory<br />

Table PD-6 — Evaporator Fan Performance — <strong>12½</strong> Ton — WC*150B — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.<strong>20</strong> 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

3 HP Standard Motor & Drive 3 HP Standard Motor & High Static Drive Accessory<br />

4000 786 1.70 815 1.82 843 1.94 870 2.06 897 2.<strong>20</strong> 923 2.34 949 2.48 974 2.64 998 2.80 1022 2.96<br />

4500 806 2.06 833 2.18 860 2.30 886 2.43 912 2.56 937 2.69 962 2.83 986 2.98 1010 3.13 1033 3.28<br />

5000 830 2.47 855 2.61 880 2.74 905 2.88 930 3.01 954 3.15 978 3.29 1001 3.43 1024 3.58 1047 3.73<br />

5500 860 2.92 883 3.08 906 3.24 929 3.39 952 3.54 975 3.69 997 3.84 10<strong>20</strong> 3.99 1042 4.14 1064 4.29<br />

6000 893 3.43 915 3.59 936 3.77 957 3.94 978 4.12 999 4.29 10<strong>20</strong> 4.46 1041 4.62 1062 4.78 1083 4.94<br />

5 HP Oversized Motor & Drive<br />

Fan motor heat (MBH) = 3.15 x Fan BHP.<br />

Data includes pressure Drop Due to Wet Coils and Filters.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-19 to determine add’l static pressure drop<br />

due to other options/accessories.<br />

Notes:<br />

1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt may be<br />

necessary.<br />

<strong>Trane</strong>'s factory supplied motors, in commercial equipment, are definite<br />

purpose motors, specifically designed and tested to operate reliably and<br />

continuously at all cataloged conditions, Using the full horsepower range<br />

of our fan motors as shown in our tabulated data will not result in nuisance<br />

tripping or premature motor failure. Our product's warranty will not be<br />

affected.<br />

16 PKGP-PRC001-EN