OPERATIONAL PROCEDURE - <strong>Elster</strong> <strong>LCR</strong>-<strong>212</strong> <strong>Single</strong> <strong>Phase</strong><br />
<strong>Load</strong> <strong>Control</strong> Ripple Receiver Installation and<br />
Use<br />
CEOP8086<br />
3.2 Time Base<br />
The time base is normally derived from the mains frequency. However, it can also optionally<br />
be derived from the crystal oscillator of the microcontroller.<br />
3.3 Internal Clock<br />
The internal clock can be set at a fixed time by a special conventional telegram. Through<br />
the use of VERSACOM, it is possible to synchronise the receiver's clock at any chosen time.<br />
3.4 Microcontroller<br />
3.4.1 Memory<br />
The processor has an integrated ROM, RAM and EEPROM to store parameters and status<br />
data. Status data is stored in the RAM, while parameters transmitted by means of remote<br />
programming are stored in the EEPROM.<br />
3.4.2 Serial Interface<br />
The receiver has a standard RS232 electrical or optical interface which is used for<br />
programming and for reading out status data.<br />
3.5 Power Supply<br />
The standard version of the <strong>LCR</strong><strong>212</strong> is designed for 230/240. The power supply unit, which<br />
is capable of withstanding short circuits, supplies the stabilised power supply voltage for the<br />
individual function groups. It is designed so as to sustain functions in the event of a supply<br />
interruption lasting up to 1.5 seconds.<br />
3.6 Output Relays<br />
With the use of plug-in 40A relays, users have the possibility of fitting up to three relays in<br />
the receiver (see installation and connection diagram).<br />
Relay status is also refreshed every 40 seconds, provided the relays have been triggered<br />
once by means of a switching command or a switching program after connection of the<br />
mains or restoration of the mains power after a failure. This allows correction of<br />
unauthorised relay status changes (anti-tamper).<br />
3.7 Real Time Clock (Optional)<br />
Voltage interruptions of up to approximately 72 hours can be bridged using a real time clock<br />
and supercap. It is possible to use the receiver as a self sufficient remotely controllable<br />
timer in this way.<br />
<strong>LCR</strong>-<strong>212</strong> receivers that have the real time clock option fitted are issued under the acronym<br />
of <strong>LCR</strong>-<strong>212</strong>RTC.<br />
22 March 2011 - Issue 3<br />
Approved By: General Manager Technical Services<br />
Page 8 of 17<br />