UNCLASSIFIED<br />

OPERATIONAL PROCEDURE - <strong>Elster</strong> <strong>LCR</strong>-<strong>212</strong> <strong>Single</strong> <strong>Phase</strong><br />

<strong>Load</strong> <strong>Control</strong> Ripple Receiver Installation and<br />

Use<br />

CEOP8086<br />

• random switching delay after receipt of a command (the maximum switching delay<br />

corresponds to the period of the cycle T)<br />

• retriggering<br />

• During a running period, starting of a new cycle can be initiated by means of a<br />

repeated switching command.<br />

• switching position on termination of the cyclic switching<br />

Cyclic switching can be activated by the following events:<br />

• cyclic switching command<br />

• ROS<br />

• schedule 1<br />

4.6 Signal Absence Sensing (SAS)<br />

The receiver's signal absence detection function monitors the time between two valid start<br />

pulses in the network. The following reactions can be specified if no start pulse is detected<br />

within a definable time:<br />

• relay positions of R1 – R4:<br />

o<br />

ON or OFF status<br />

o disable switching program 1-4<br />

o<br />

o<br />

terminate cyclic switching<br />

no reaction<br />

• enable Memory function<br />

• enable a schedule<br />

(enabled schedules can be disabled by means of a special command or by receipt of a<br />

valid start pulse)<br />

5 SCOPE OF FUNCTIONS<br />

5.1 Conventional Decoder<br />

5.1.1 Number of Switching Commands<br />

Up to 14 commands can be programmed for each receiver.<br />

• 4 ON switching commands or restoration timers<br />

• 4 OFF switching commands<br />

• 3 commands for cyclic switching<br />

• 1 command for time synchronisation (not using VERSACOM)<br />

• 1 command for switchover to VERSACOM decoding<br />

• 1 command for schedule disabling (not using VERSACOM)<br />

22 March 2011 - Issue 3<br />

Approved By: General Manager Technical Services<br />

Page 10 of 17<br />

UNCLASSIFIED<br />

UNCONTROLLED COPY IF PRINTED