16.09.2014 Views

caution - Toro

caution - Toro

caution - Toro

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

2. Conduct a hydrometer test of the battery electrolyte.<br />

IMPORTANT: Make sure the area around the cells is<br />

clean before opening the battery caps.<br />

A. Measure the specific gravity of each cell with a<br />

hydrometer. Draw electrolyte in and out of the<br />

hydrometer barrel prior to taking a reading to warm--<br />

up the hydrometer. At the same time take the temperature<br />

of the cell.<br />

B. Temperature correct each cell reading. For each<br />

10 o F(5.5 o C) above 80 o F (26.7 o C) add 0.004 to the<br />

specific gravity reading. For each 10 o F(5.5 o C) below<br />

80 o F (26.7 o C) subtract 0.004 from the specific<br />

gravity reading.<br />

Example: Cell Temperature<br />

100 o F<br />

Cell Gravity 1.245<br />

100 o F minus 80 o F equals 20 o F<br />

(37.7 o C minus 26.7 o C equals 11.0 o C)<br />

20 o F multiply by 0.004/10 o F equals 0.008<br />

(11 o C multiply by 0.004/5.5 o C equals 0.008)<br />

ADD (conversion above) 0.008<br />

Correction to 80 o F (26.7 o C) 1.253<br />

C. If the difference between the highest and lowest<br />

cell specific gravity is 0.050 or greater or the lowest<br />

cell specific gravity is less than 1.225, charge the battery.<br />

Charge at the recommended rate and time given<br />

in Charging or until all cells specific gravity is<br />

1.225 or greater with the difference in specific gravity<br />

between the highest and lowest cell less than 0.050.<br />

If these charging conditions can not be met, replace<br />

the battery.<br />

3. Perform a high--discharge test with an adjustable<br />

load tester.<br />

This is one of the most reliable means of testing a battery<br />

as it simulates the cold--cranking test. A commercial battery<br />

load tester is required to perform this test.<br />

B. If the battery has recently been charged, apply a<br />

150 amp load for 15 seconds to remove the surface<br />

charge. Use a battery load tester following the<br />

manufacturer’s instructions.<br />

C. Make sure battery terminals are free of corrosion.<br />

D. Measure the temperature of the center cell.<br />

E. Connect a battery load tester to the battery terminals<br />

following the manufacturer’s instructions.<br />

Connect a digital multimeter to the battery terminals.<br />

F. Apply a test load of 325 amps (one half the battery<br />

cold cranking amp rating) for 15 seconds.<br />

G. Take a battery voltage reading at 15 seconds,<br />

then remove the load.<br />

H. Using the table below, determine the minimum<br />

voltage for the cell temperature reading:<br />

Minimum<br />

Voltage<br />

Battery Electrolyte<br />

Temperature<br />

9.6 70 o F (and up) 21.1 o C (and up)<br />

9.5 60 o F 15.6 o C<br />

9.4 50 o F 10.0 o C<br />

9.3 40 o F 4.4 o C<br />

9.1 30 o F -- 1.1 o C<br />

8.9 20 o F -- 6.7 o C<br />

8.7 10 o F --12.2 o C<br />

8.5 0 o F --17.8 o C<br />

I. If the test voltage is below the minimum, replace<br />

the battery. If the test voltage is at or above the minimum,<br />

return the battery to service.<br />

Electrical<br />

System<br />

CAUTION<br />

Follow the manufacturer’s instructions when using<br />

a battery tester.<br />

A. Check the voltage across the battery terminals<br />

prior to testing the battery. If the voltage is less than<br />

12.4 VDC, charge the battery before continuing with<br />

load testing procedure.<br />

Groundsmaster 4100--D Page 5 - 39 Electrical System

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!