RECOMMENDED LINE SIZING for AIR COOLED SPLIT SYSTEMS<br />

HOT GAS LINES – SINGLE CIRCUIT UNITS (Up To 200 Equivalent Feet)<br />

Tonnage Tons/Circuit 50 feet 100 feet 150 feet 200 feet<br />

2.5 2.5 5/8 7/8 7/8 7/8<br />

3 3 7/8 7/8 7/8 7/8<br />

4 4 7/8 7/8 7/8 1-1/8<br />

5 5 7/8 1-1/8 1-1/8 1-1/8<br />

LIQUID LINES – SINGLE CIRCUIT UNITS (Up to 200 Equivalent Feet)<br />

Tonnage Tons/Circuit 50 feet 100 feet 150 feet 200 feet<br />

2.5 2.5 3/8 1/2 1/2 1/2<br />

3 3 1/2 1/2 1/2 1/2<br />

4 4 1/2 5/8 5/8 5/8<br />

5 5 1/2 5/8 5/8 5/8<br />

SUCTION LINES – SINGLE CIRCUIT UNITS (Up to 200 Equivalent Feet)<br />

Tonnage<br />

Tons per<br />

Circuit<br />

50 feet<br />

HOR VER<br />

100 feet<br />

HOR VER<br />

150 feet<br />

HOR VER<br />

200 feet<br />

HOR VER<br />

2.5 2.5 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8<br />

3 3 7/8 7/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8<br />

4 4 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8<br />

5 5 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8<br />

HOR = HORIZONTAL<br />

VER = VERTICAL<br />