RECOMMENDED LINE SIZING for AIR COOLED SPLIT SYSTEMS<br />
HOT GAS LINES – SINGLE CIRCUIT UNITS (Up To 200 Equivalent Feet)<br />
Tonnage Tons/Circuit 50 feet 100 feet 150 feet 200 feet<br />
2.5 2.5 5/8 7/8 7/8 7/8<br />
3 3 7/8 7/8 7/8 7/8<br />
4 4 7/8 7/8 7/8 1-1/8<br />
5 5 7/8 1-1/8 1-1/8 1-1/8<br />
LIQUID LINES – SINGLE CIRCUIT UNITS (Up to 200 Equivalent Feet)<br />
Tonnage Tons/Circuit 50 feet 100 feet 150 feet 200 feet<br />
2.5 2.5 3/8 1/2 1/2 1/2<br />
3 3 1/2 1/2 1/2 1/2<br />
4 4 1/2 5/8 5/8 5/8<br />
5 5 1/2 5/8 5/8 5/8<br />
SUCTION LINES – SINGLE CIRCUIT UNITS (Up to 200 Equivalent Feet)<br />
Tonnage<br />
Tons per<br />
Circuit<br />
50 feet<br />
HOR VER<br />
100 feet<br />
HOR VER<br />
150 feet<br />
HOR VER<br />
200 feet<br />
HOR VER<br />
2.5 2.5 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 7/8<br />
3 3 7/8 7/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8<br />
4 4 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8<br />
5 5 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 1-1/8 1-3/8 1-1/8<br />
HOR = HORIZONTAL<br />
VER = VERTICAL<br />