8.5 Fuses<br />

Fuses may occasionally require changing especially with installations where the voltage is not<br />

consistent. Drops in voltage can create brief periods of high amp draw, causing fuses to blow.<br />

Always replace fuses with those of the equivalent rating with regard to: 1) amperage, 2) voltage<br />

<strong>and</strong> 3) speed. For instance – compressors are <strong>and</strong> motors are inductive loads which require time<br />

delay fuses where electric reheat <strong>and</strong> humidifi ers are resistive loads requiring fast acting fuses.<br />

8.6 Heating Elements<br />

Heating elements do not normally require maintenance. However, they may accumulate a fi lm of<br />

dust or dirt when unused for extended periods of time. When energized, the burning debris can<br />

create smoke or an unpleasant odor. To help avoid a problem, periodic cleaning is recommended.<br />

8.7 Refrigerant Filter Drier<br />

Factory installed refrigerant fi lter driers do not require maintenance or replacement unless the system<br />

has been opened. When replacing compressors or other repairs that open the refrigeration<br />

system to the atmosphere, it is always advisable to replace the fi lter drier. The equivalent type<br />

<strong>and</strong> size should be used.<br />

33