6.0 GLYCOL SYSTEMS<br />

6.1 Glycol Concentration<br />

The system must be fi lled with water <strong>and</strong> the appropriate amount of ethylene or propylene glycol<br />

to protect against winter freezing. To achieve the approximate glycol concentration, it is necessary<br />

to know the total system volume. The total system volume consists of the fl uid cooler volume, the<br />

evaporator unit volume <strong>and</strong> the volume of the inter-connecting piping.<br />

The following tables can be used for arriving at an approximate system volume. After installation,<br />

the glycol percentage should be checked. The glycol percentage should be checked at regular<br />

intervals to ensure against freeze protection.<br />

6.2 Internal (Fluid) Volume<br />

Evaporator Model<br />

Volume (gallons) - no Energy<br />

Saver Coil<br />

Volume (gallons) – with Energy<br />

Saver Coil<br />

DAPG 2.5 1.0 2.5<br />

DAPG 03 1.0 2.5<br />

DAPG 04 2.5 4.0<br />

DAPG 05 2.5 4.0<br />

6.3 Fluid Cooler Internal Volume<br />

Fluid Cooler Volume (gallons) Fluid Cooler Volume (gallons)<br />

DAFC 06 2.5 DAFC 17 6.6<br />

DAFC 07 3.4 DAFC 21 7.4<br />

DAFC 09 4.2 DAFC 24 9.8<br />

DAFC 11 3.3 DAFC 29 12.3<br />

DAFC 15 4.9<br />

6.4 Copper Piping Internal Volume<br />

Pipe Diameter Inches O.D.<br />

Volume per 100 feet of Pipe (gallons)<br />

5/8 1.2<br />

3/4 1.8<br />

7/8 2.5<br />

1-1/8 2.5<br />

1-5/8 4.3<br />

2-1/8 9.2<br />

28