5.4 Refrigerant H<strong>and</strong>ling<br />

The use of recovery/recycling is required by the US Environmental Protection Agency (EPA) regulations.<br />

Technicians who service <strong>and</strong> dispose of air conditioning <strong>and</strong> refrigeration equipment must<br />

recover the refrigerant instead of venting to the atmosphere.<br />

Except for extremely small releases of refrigerant such as those that occur when disconnecting<br />

service hoses (diminutive release), a technician who knowing releases or vents refrigerant to the<br />

atmosphere is in violation of these regulations. Freon purchasers must be certifi ed technicians<br />

<strong>and</strong> have a valid EPA certifi cation card.<br />

Warning! Pressure relief lines(s) must be vented to the atmosphere per the latest edition<br />

of ASHRAE St<strong>and</strong>ard 15 <strong>and</strong>/or any local building, fire or mechanical codes.<br />

This applies to all units with either sell <strong>and</strong> tube condensers or high pressure relief valve<br />

options.<br />

5.5 Important Refrigeration Components<br />

5.5.1 Expansion Vale<br />

Each refrigerant circuit has an adjustable thermo-expansion valve (TXV). They are factory adjusted<br />

to their nominal rating. Any fi eld adjustment should be to “fi ne tune” a system that has been<br />

stabilized <strong>and</strong> already has acceptable operating parameters.<br />

5.5.2 High Pressure Cutout Switch<br />

Each refrigeration circuit is protected by a high head pressure cutout switch with a manual reset<br />

button. The switch is located near the compressor.<br />

The pressure rating for R-407C systems is 400 PSIG.<br />

The pressure rating for R-410A systems is 610 PSIG.<br />

5.5.3 Low Pressure Cutout Switch<br />

Each circuit includes a low pressure cutout switch with automatic reset. The switch is located near<br />

the compressor section.<br />

The pressure rating for R-407C systems is 28 PSIG.<br />

The pressure rating for R-410A systems is 50 PSIG.<br />