4.0 INSTALLATION OF REMOTE OUTDOOR HEAT EXCHANGER<br />

Air cooled condenser <strong>and</strong> fl uid coolers have individual <strong>Installation</strong>, <strong>Operation</strong> <strong>and</strong> <strong>Maintenance</strong><br />

manuals which should be referred to for more complete details<br />

4.1 Rigging<br />

The following covers outdoor condensers, condensing units <strong>and</strong> fl uid coolers. Outdoor heat exchangers<br />

should be moved to their mounting location using a crane or fork lift as applicable. Each<br />

fan section has supports with lifting holes at the top.<br />

Do not lift with a choke sling around the unit. Spreader bars are recommended for lifting multiple<br />

fan units. Under no circumstances should the coil headers or piping be used for lifting the unit.<br />

The unit should be kept in its shipping crate until it is ready to be set in place.<br />

4.2 Leg Assembly<br />

The legs of the remote heat exchanger are shipped with the unit in the “collapsed” position <strong>and</strong><br />

need to be lowered during the rigging process. The legs must be unbolted from their collapsed<br />

position <strong>and</strong> extended prior to placing the units on its pad. Each leg extends down 18 inches <strong>and</strong><br />

should be reattached using the same bolts. The bolts are placed through the lower set of holes on<br />

the bracket. Multiple fan units have leg supports between each section.<br />

Concrete pads or a rail system are often used to provide support for the heat exchanger. Bolt<br />

holes in the bottom of each leg can be used to anchor the unit.<br />

DARC-03 <strong>and</strong> DARC-05 units do not have legs <strong>and</strong> are ready for installation.<br />

WARNING: Failure to extend the legs will result in poor air distribution over the cooling<br />

coil resulting in signifi cant capacity reduction <strong>and</strong> potential high discharge pressure<br />

problems.<br />

4.3 Locating the Remote Heat Exchanger<br />

The remote heat exchanger must be located in an area that will ensure free air fl ow into <strong>and</strong> out<br />

of the heat exchanger plus adequate service access clearance. Short circuiting of the air fl ow or<br />

the intake of warmer air from another unit will seriously degrade the performance of the air cooled<br />

heat exchanger.<br />