the panel. Although these existing sensors can be removed for remote mounting, the remote sensor<br />

option provides a more convenient means of fi eld installation. When ordered, the remote sensors<br />

are shipped with a predetermined length of cable <strong>and</strong> come mounted in a plastic enclosure.<br />

The temperature <strong>and</strong> humidity sensors require a total of six wires. These wires should be twisted<br />

pair, shielded type (minimum of 18 gauge).<br />

3.8.2 Mini DAP-III Units<br />

The optional Mini DAP-III microprocessor control panel normally comes with the sensors mounted<br />

in the display module. Although these existing sensors can be removed for remote mounting, the<br />

remote sensor option provides a more convenient means of fi eld installation. When ordered, the<br />

remote sensors are shipped with a predetermined length of cable <strong>and</strong> come mounted in a plastic<br />

enclosure. The temperature <strong>and</strong> humidity sensors require a total of fi ve wires. These wires should<br />

be 18 gauge, twisted pair, shielded type.<br />

3.9 Condensate Pumps<br />

The optional condensate pump that’s shipped loose normally require a separate power source<br />

(110 volt). Always check the pump power requirements before connecting power. Condensate<br />

pumps are available in other voltages.<br />

Optional condensate pumps that are factory wired <strong>and</strong> mounted do not require any additional wiring<br />

or a separate power source. However, fi eld piping is still required.<br />