2.2.1 Field Piping, Water/Glycol System<br />

2.2.2 Connection Sizes, Water/Glycol Cooled Units<br />

EVAPORATOR MODEL WATER IN CONNECTION WATER OUT CONNECTION<br />

DAPW/G-2.5 3/4” O.D. 3/4” O.D.<br />

DAPW/G-03 3/4” O.D. 3/4” O.D.<br />

DAPW/G-04 1-1/8” O.D. 1-1/8” O.D.<br />

DAPW/G-05 1-1/8” O.D. 1-1/8” O.D.<br />

2.2.3 Connection Sizes, Fluid Coolers (Dry Coolers)<br />

EVAPORATOR MODEL WATER IN CONNECTION WATER OUT CONNECTION<br />

DAFC-06 1-5/8” O.D. 1-5/8” O.D.<br />

DAFC-07 1-5/8” O.D. 1-5/8” O.D.<br />

DAFC-09 1-5/8” O.D. 1-5/8” O.D.<br />

DAFC-11 2-1/8” O.D. 2-1/8” O.D.<br />

DAFC-15 2-1/8” O.D. 2-1/8” O.D.<br />

DAFC-17 2-5/8” O.D. 2-5/8” O.D.<br />

2.3 Auxiliary Chilled Water Coil Piping<br />

Units with an optional Auxiliary Chilled Water cooling coil require a separate source of chilled<br />

water. The chilled water connection sizes will be the same as those listed for the condenser water<br />

(see chart in Section 2.2.3). Units with optional Energy Saver coil typically have shared or common<br />

piping with the condenser supply <strong>and</strong> therefore do not require a separate cooling source.<br />

13