<strong>Chip</strong>BLASTER, Inc. 110<br />
27.0. OPTIONAL EQUIPMENT (Cont.):<br />
27.21. OPTIONAL DROP IN CHILLER (Cont.):<br />
27.21.8.2. AIR FILTER: Keep Clean<br />
27.21.8.3. CONDENSER: Condenser fins should be cleaned of dust and dirt<br />
regularly.<br />
27.21.8.4. PUMP: See attached pump instructions.<br />
27.21.9. TROUBLE SHOOTING<br />
PROBLEM CAUSE SOLUTION<br />
Cooler operative A. Low Coolant Level Add Coolant<br />
but not cooling B. Dirty Air Filter Clean<br />
C. Blocked Air Flow Remove Blockage<br />
D. Condenser Clogged Clean<br />
E. Faulty Controller Repair/Replace<br />
F. Low Refrigerant Charge Repair *<br />
G. Faulty Compressor Repair/Replace *<br />
H. Faulty Solenoid Valve/ Replace *<br />
Coil<br />
I. Incorrect Expansion Adjust Expansion Valve to proper setting *<br />
Valve setting<br />
Cooler inoperative A. Faulty Power Source Check & Correct<br />
or does not start B. Cooler OFF on Low Check for:<br />
Pressure<br />
Low Coolant Level<br />
No Coolant Flow across the coils<br />
Low Ambient<br />
Wrong Setting on Pressure Switch<br />
Low or Lost Refrigerant Charge *<br />
Incorrect Expansion Valve Setting *<br />
• Actions designated with * should only be done by a Qualified Refrigeration Service Person.<br />
check with factory for proper settings.<br />
27.21