Parameter Overview<br />
Operation manual<br />
11<br />
A109 PZD-Timeout:<br />
To <strong>keep</strong> the inverter from continuing with the last received reference values after<br />
a failure of PROFIBUS or the PROFIBUS master, process data monitoring<br />
should be activated. The RX block monitors the regular receipt of process data<br />
telegrams (PZD) which the PROFIBUS master sends cyclically during normal<br />
operation. The A109 PZD-Timeout parameter is used to activate this monitoring<br />
function. A time is set here in milliseconds. The default setting is 65535. This<br />
value and also the value 0 mean that monitoring is inactive. This is<br />
recommended while the inverter is being commissioned on PROFIBUS and for<br />
service and maintenance work.<br />
Monitoring should only be activated for the running process during which a bus<br />
master cyclically sends process data to the inverter. The monitoring time must<br />
be adapted to the maximum total cycle time on PROFIBUS plus a sufficient<br />
reserve for possible delays on the bus. Sensible values are usually bet<strong>we</strong>en 30<br />
and 300 msec.<br />
When process data monitoring is triggered on the inverter, the fault<br />
"52:communication" is triggered.<br />
* The A109 PZD-Timeout parameter is also used for communication via USS<br />
protocol for the USS-PZD telegram.<br />
Axes: Global<br />
Data type:<br />
Value:<br />
PNU:<br />
206D hex<br />
Subindex:<br />