Parameter Overview<br />

Operation manual<br />

11<br />

11.3 List of the primary communication parameters<br />

You will need the following parameters when commissioning an inverter on<br />

PROFIBUS:<br />

A00 Save values & start:<br />

When this parameter is activated, the inverter saves the current configuration<br />

and the parameter values in the Paramodule. After po<strong>we</strong>r-off, the inverter starts<br />

with the saved configuration. If the configuration data on the inverter and<br />

Paramodul are identical, only the parameters are saved (speeds up the<br />

procedure).<br />

NOTE<br />

Do not turn off the po<strong>we</strong>r of the control section (device version /L:24V, device<br />

version /H: supply voltage) while the action is being executed. If the po<strong>we</strong>r is<br />

turned off while the action is running this causes incomplete storage. After the<br />

device starts up again the fault "*<strong>Co</strong>nfigStartERROR parameters lost" appears<br />

on the display.<br />

Only several 1000 storage procedures are possible per Paramodul. When this<br />

limit has almost been reached, result 14 is indicated after the storage procedure.<br />

When this happens, replace Paramodul as soon as possible.<br />

Axes: Global<br />

Data type: —<br />

Value: 0, 0, 0<br />

PNU:<br />

2000 hex<br />

Subindex: 3<br />

A83 Busaddress:<br />

Specifies the device address for operation with fieldbus. A83 has no effect on<br />

communication via X3 with POSITool or another USS master.<br />

Axes: Global<br />

Data type: 5<br />

Value: 3<br />

PNU:<br />

2053 hex<br />

Subindex: 1<br />

A84 PROFIBUS Baudrate:<br />

When operated with a device of the 5 th generation of STÖBER inverters with<br />

option board "PROFIBUS DP," the baud rate found on the bus is indicated.<br />

Axes: Global<br />

Data type: 5<br />

Value: 0=9600 Baud, ...<br />

PNU:<br />

2054 hex<br />

Subindex: 1<br />

WE KEEP THINGS MOVING<br />

ID 441687.03<br />