Bus diagnosis/LEDs<br />

Operation manual<br />

6<br />

The following diagnostic capabilities are available:<br />

• The two LEDs on the option board DP 5000<br />

• Parameter A84 PROFIBUS Baudrate<br />

• Parameter A86 PROFIBUS configuration<br />

• Parameter A85 PROFIBUS diagnosis (indication of internal inverter<br />

diagnostic information via the PROFIBUS interface).<br />

Parameter A85 is composed of the following bits:<br />

Bit Name Meaning for Bit = 1<br />

0 Shutdown-Fail Problems during shutting down the PROFIBUS driver<br />

software<br />

1 Data-Exchange PROFIBUS is in the state of cyclic data communication<br />

with this station.<br />

2 Wait for Param Station is waiting to be parameterized by the<br />

PROFIBUS master.<br />

3 Bus-Failure Error on PROFIBUS<br />

4 Acyc. Initiate 1 An acyclic connection has been established.<br />

5 Acyc. Initiate 2 A second acyclic connection has been established.<br />

6 MDS configured Station has been configured by the PROFIBUS master.<br />

7 Driver-Error Error in the PROFIBUS driver software.<br />

8 Application ready Inverter firmware is ready for a connection to<br />

PROFIBUS.<br />

9 LED red on The red LED of the DP 5000 is now on.<br />

10 LED green on The green LED of the DP 5000 is now on.<br />