Bus diagnosis/LEDs<br />
Operation manual<br />
6<br />
The following diagnostic capabilities are available:<br />
• The two LEDs on the option board DP 5000<br />
• Parameter A84 PROFIBUS Baudrate<br />
• Parameter A86 PROFIBUS configuration<br />
• Parameter A85 PROFIBUS diagnosis (indication of internal inverter<br />
diagnostic information via the PROFIBUS interface).<br />
Parameter A85 is composed of the following bits:<br />
Bit Name Meaning for Bit = 1<br />
0 Shutdown-Fail Problems during shutting down the PROFIBUS driver<br />
software<br />
1 Data-Exchange PROFIBUS is in the state of cyclic data communication<br />
with this station.<br />
2 Wait for Param Station is waiting to be parameterized by the<br />
PROFIBUS master.<br />
3 Bus-Failure Error on PROFIBUS<br />
4 Acyc. Initiate 1 An acyclic connection has been established.<br />
5 Acyc. Initiate 2 A second acyclic connection has been established.<br />
6 MDS configured Station has been configured by the PROFIBUS master.<br />
7 Driver-Error Error in the PROFIBUS driver software.<br />
8 Application ready Inverter firmware is ready for a connection to<br />
PROFIBUS.<br />
9 LED red on The red LED of the DP 5000 is now on.<br />
10 LED green on The green LED of the DP 5000 is now on.<br />