28.08.2014 Views

we keep things moving - STÖBER ANTRIEBSTECHNIK GmbH + Co ...

we keep things moving - STÖBER ANTRIEBSTECHNIK GmbH + Co ...

we keep things moving - STÖBER ANTRIEBSTECHNIK GmbH + Co ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Bus diagnosis/LEDs<br />

Operation manual<br />

6<br />

6 Bus diagnosis/LEDs<br />

The DP 5000 option module is equipped with a green and a red LED. The LEDs<br />

indicate communication-specific states. This permits the PROFIBUS status to be<br />

diagnosed on the device.<br />

RED<br />

GREEN<br />

Fig. 6-1: View on LED<br />

Red LED Green Bedeutung/Maßnahme<br />

LED<br />

Off Off No connection bet<strong>we</strong>en the inverter and the PROFIBUS<br />

board (board was not recognized or has failed. See<br />

parameter E54 option module 1).<br />

Flashing Off PROFIBUS master stopped bus for more than 25 s (PLC in<br />

stop) or has failed or bus cable no longer connected (see<br />

parameter A84 PROFI-Baud).<br />

Off Flashing Device is ready and is waiting for the PROFIBUS master to<br />

start or:When this state does not change although the<br />

PROFIBUS master has already attempted to establish a<br />

connection, this means that the applicable function blocks<br />

for PROFIBUS have not been downloaded to the inverter.<br />

Off On Device was configured by PROFIBUS master and data<br />

communication was started.<br />

Flashing Flashing PROFIBUS master stopped the bus just a few seconds ago<br />

(< 25 s) (PLC in stop) or has failed or bus cable is no longer<br />

connected (see parameter A84 PROFI-Baud).<br />

WE KEEP THINGS MOVING<br />

ID 441687.03<br />

23