4.7.3 Limitations<br />

Balanced safety-relief valves should not be used:<br />

• on ASME BPVC Section I steam boiler drums or ASME BPVC Section I superheaters,<br />

and<br />

• as pressure control or bypass valves.<br />

Balanced type valves require vented bonnets. A bellows failure allows process media from<br />

the discharge side of the valve to discharge from the bonnet vent. Consider the nature of<br />

the process media (e.g. liquid/vapor, toxicity, and flammability) when evaluating the<br />

bonnet vent disposition. Bonnet vents are typically routed to a drain or atmosphere<br />

depending on the process media involved.<br />

Fion Zhnag/ Charlie Chong