when a valve operates in nonfouling service, experience may indicate that<br />

inspection of the valve while on the equipment is safe and suitable.<br />

• Bonnet removed, visual inspection and minor repairs.<br />

• Testing for set pressure with inert gas testing medium through a<br />

bleeder.<br />

• If insufficient volume to attain about half lift, It yields inaccurate<br />

test results for metal-seated pressure-relief valves and the use of a<br />

restricted lift device is recommended to avoid damaging the valve by<br />

too rapid of a closure.<br />

• A pressure-relief valve may be tested on-stream with a specialized<br />

hydraulically lift device that will determine the set pressure (not<br />

blowdown).<br />

Fion Zhang/ Charlie Chong