Normally, the deviation of the pop pressure from the set<br />

pressure should not exceed;<br />

±2 psi for pressure ≤ 70 psi<br />

±3 % for pressure > 70psi<br />

[see ASME BPVC Section VIII, Division 1, Paragraph UG 134(d)(1)].<br />

Within 0 % or +10 %.<br />

[see ASME BPVC Section VIII, Division 1, Paragraph UG 125(c)(3)].<br />

Any allowance for hot setting should be made in accordance with the<br />

manufacturer's data. Any adjustment to the CDTP required to<br />

compensate for (1) in-service backpressure, (2) service temperature, or<br />

(3) test media should be made in accordance with the manufacturer's or<br />

user’s valve specification data.<br />