TC-32<br />

Technical characteristics<br />

IEC style overload relays<br />

®<br />

electric<br />

TC<br />

Operational<br />

characteristics<br />

thermal overload<br />

relays RF<br />

Phase failure sensitive hand reset RF9 RF38❶ RF25 RF95 RF200❶ RF420❶<br />

Phase failure sensitive automatic reset RFA9 RFS38❶ RFA25 RFA95<br />

Non phase failure sensitive hand reset RFS25 RFS95<br />

Non phase failure sensitive automatic reset<br />

POWER CIRCUIT CHARACTERISTICS<br />

Rated insulation voltage Ui V 690 690 690 690 1000 1000<br />

Rated impulse withstand voltage Uimp kV 8<br />

Frequency limit Hz 0 - 400 0 - 400 0 - 400 0 - 400 50 - 60 50 - 60<br />

Operational range from A 0.09 0.1 0.09 14 60 150<br />

to A 15 38 26 95 200 420 ❷<br />

Connection Direct With current transformers ❸<br />

Terminals<br />

Yoke<br />

Type Screw & washer clamp Screw & flat washer<br />

Screw M 4 M 4 M 4 M 5 M 8 (hex) M 10 (hex)<br />

Terminal width in 0.4 0.5 0.4 0.35 0.8 1<br />

(mm) (9.8) (12.6) (9.8) (9) (20) (25)<br />

Phillips n° 2 2 2 2 13mm❹ 18mm❹<br />

Tightening torque Nm 2.3 2...2.5 2.3 3.9 18 35<br />

for power terminals lbft 1.7 1.5...1.8 1.7 2.88 13.3 25.9<br />

Maximum conductor section connectable<br />

AWG n° 10 8 10 2 -- --<br />

flexible w/o lug mm 2 6 10 6 35 -- --<br />

flexible c/w lug mm 2 10 6 10 -- 150 2 - 150<br />

Bar<br />

in<br />

(mm) -- -- -- -- (25 x 3) (30 x 5)<br />

Dissipation per phase W 0.7 - 2.4 0.7 - 2.40 0.7 - 2.4 2 - 4.2 0.7 - 2.4 0.7 - 2.4<br />

AUXILIARY CIRCUIT CHARACTERISTICS<br />

Available NO n° 1<br />

contacts NC n° 1<br />

Rated insulation voltage V 690<br />

Conventional free air thermal current A 10<br />

Terminals with Screw M3.5<br />

screw and washer Terminal width 0.3 in (8mm)<br />

Phillips n° 1<br />

Maximum conductor section connectable<br />

Flexible w/o lug mm 2 2.5<br />

Flexible c/w lug mm 2 2.5<br />

Tightening torque Nm 1 1...1.5 1 1 1...1.5 1...1.5<br />

for auxiliary terminals lbft 0.74 0.74...1.1 0.74 0.74 0.74...1.1 0.74...1.1<br />

UL designation (IEC/EN 60947-5-1) AC-DC B600 - P600 B600-R300 B600-P600 B600-P600 B600-R300 B600-R300<br />

❺ ❺ ❺<br />

Operational current AC (220-230V) A 2.5<br />

DC (110V) A 1.1<br />

AMBIENT CONDITIONS<br />

Operating temperature °F -4 to +130 -13 to +140 -4 to +130 -4 to +130 -13 to +140 -13 to +140<br />

°C (-20 to +55) (-25 to +60) (-20 to +55) (-20 to +55) (-25 to +60) (-25 to +60)<br />

Storage temperature °F -65 to +160 -60 to +160 -65 to +160 -65 to +160 -60 to +160 -60 to +160<br />

°C (-55 to +70) (-50 to +70) (-55 to +70) (-55 to +70) (-50 to +70) (-50 to +70)<br />

Compensation temperature °F +5 to +160 -4 to +140 +5 to +160 +5 to +160 -4 to +140 -4 to +140<br />

°C (-15 to +55) (-20 to +60) (-15 to +55) (-15 to +55) (-20 to +60) (-20 tp +60)<br />

Maximum altitude ft 9800 (3000m)<br />

Operation position Normal On vertical plane<br />

Allowable ±30°<br />

Mounting<br />

On contactor or separately<br />

Tripping class<br />

10A<br />

Particular characteristics<br />

Test button - Trip indicator<br />

❶ With manual and automatic resetting.<br />

❷ For currents higher than 420A, contact Sales & Technical Support.<br />

❸ Standard supplied.<br />

❹ Metric wrench/spanner.<br />

❺ C600-R300 for automatic reset type.<br />

Sold by <strong>AA</strong> <strong>Electric</strong> 1-800-237-8274 • Lakeland, FL • Lawrenceville, GA • East Rutherford, NJ<br />

Web : www.A-Aelectric.com Email: njsales@a-aelectric.com