TC-20<br />

Technical characteristics<br />

IEC style contactors<br />

®<br />

electric<br />

TC<br />

Operational<br />

characteristics<br />

BF9-BF40 with AC<br />

or DC control<br />

circuit<br />

TYPE<br />

POLE CHARACTERISTICS<br />

Power poles n°<br />

Rated insulation voltage Ui<br />

V<br />

Rated impulse withstand votage Uimp kV<br />

Operational frequency<br />

Hz<br />

Operational Conventional free air<br />

current thermal Ith (≤105°F/≤40°C) A<br />

AC3 (≤440V ≤130°F/≤55°C) A<br />

AC4 (400V)❹<br />

A<br />

Short-time allowable current for 10s<br />

(IEC/EN 60947-1)<br />

A<br />

BF9C BF12C BF16C BF20C BF25C BF32C BF40C❶ BF40C 40❷<br />

3-4 3 3-4 3 3-4 3 3 4<br />

690<br />

8<br />

25-400❸<br />

25 25 25 40 40 55 60 60<br />

9 12 16 20 25 32 40 40<br />

5.3 7.2 7.5 10 11.7 16 20 20<br />

110 110 130 160 200 320 320 320<br />

Max fuse size SC/gG A 32 40 40 50 50 63 80 80<br />

Type 1 or 2 aM A 10 12 16 20 25 32 40 40<br />

Making capacity (RMS value) A<br />

210 210 210 350 350 480 480 480<br />

Breaking capacity ≤440V A 210 210 210 350 350 480 480 480<br />

at voltage<br />

500V A 160 160 160 290 290 320 320 320<br />

690V A 120 120 120 220 220 270 270 270<br />

Consumption and<br />

mΩ 5 5 5 2.5 2.5 2.0 1.8 1.8<br />

resistance per pole<br />

Ith W 3.1 3.1 3.1 4.0 4.0 6.0 6.5 6.5<br />

(average values)<br />

AC3 W 0.40 0.72 1.3 1.0 1.6 2.0 2.6 2.6<br />

Terminals in. (mm)<br />

Type<br />

Clamp-screw<br />

A<br />

0.32 (8.3) 0.4 (10.1) 0.52 (13.2)<br />

B<br />

0.14 (3.5) 0.23 (5.9) 0.22 (5.5)<br />

A<br />

Screw M3.5 M3.5 M3.5 M4 M4 M5 M5 M5<br />

Phillips 2 2 2 2 2 2 2 2<br />

Min-Max tightening torque<br />

Nm 1.4-1.8 1.4-1.8 1.4-1.8 1.8-2.3 1.8-2.3 3.1-3.9 3.1-3.9 3.1-3.9<br />

for contact terminal<br />

Ibft 1.03-1.33 1.03-1.33 1.03-1.33 1.32-1.70 1.32-1.70 2.24-2.88 2.24-2.88 2.24-2.88<br />

Min-Max tightening torque<br />

Nm 0.8-1 0.8-1 0.8-1 0.8-1 0.8-1 0.8-1 0.8-1 0.8-1<br />

for coil terminals<br />

lbft 0.59-0.74 0.59-0.74 0.59-0.74 0.59-0.74 0.59-0.74 0.59-0.74 0.59-0.74 0.59-0.74<br />

Phillips 2 2 2 2 2 1 1 1<br />

Maximum conductor section<br />

connectable with 1 or 2 wires<br />

AWG n° 10 10 10 8 8 4 4 4<br />

Flexible w/o lug<br />

(min-max) mm 2 1-6 1-6 1-6 1.5-10 1.5-10 2.5-16 2.5-16 2.5-16<br />

Flexible c/w lug mm 2 6 6 6 6 6 6 6 6<br />

Power terminal protection<br />

according to EN 60529<br />

IP20❺ IP20❺ IP20❺ IP20❻ IP20❻ IP20❼ IP20❼ ––<br />

AMBIENT CONDITIONS<br />

Operating temperature<br />

Storage temperature<br />

Maximum altitude<br />

°F<br />

°F<br />

ft<br />

-60 to +160 (-50 to +70°C)<br />

-75 to +175 (-60 to +80°C)<br />

9800 (3000m)<br />

Operating<br />

position<br />

Fixing<br />

Normal<br />

Allowable<br />

On vertical plane<br />

± 30°<br />

Screw or 35mm DIN rail (IEC/EN 60715)<br />

❶ Three-pole version.<br />

❷ Four-pole version, 4NO type (main poles). For data of the 2NO+2NC type, contact Sales & Technical Support.<br />

❸ Derating for use at 61-400Hz. Contact Sales & Technical Support.<br />

❹ Current values guarantee an electrical life of about 200,000 cycles.<br />

❺ IP20 protection warranted by wired equipment; minimum 18 AWG / 1mm 2 conductor section.<br />

❻ 14 AWG / 2.5mm 2 conductor section for 3-pole type or 10 AWG / 6mm 2 for 4-pole type<br />

❼ IP20 protection warranted by wired equipment; minimum 6 AWG / 16mm 2 conductor section.<br />

B<br />

Sold by <strong>AA</strong> <strong>Electric</strong> 1-800-237-8274 • Lakeland, FL • Lawrenceville, GA • East Rutherford, NJ<br />

Web : www.A-Aelectric.com Email: njsales@a-aelectric.com