TC-20<br />
Technical characteristics<br />
IEC style contactors<br />
®<br />
electric<br />
TC<br />
Operational<br />
characteristics<br />
BF9-BF40 with AC<br />
or DC control<br />
circuit<br />
TYPE<br />
POLE CHARACTERISTICS<br />
Power poles n°<br />
Rated insulation voltage Ui<br />
V<br />
Rated impulse withstand votage Uimp kV<br />
Operational frequency<br />
Hz<br />
Operational Conventional free air<br />
current thermal Ith (≤105°F/≤40°C) A<br />
AC3 (≤440V ≤130°F/≤55°C) A<br />
AC4 (400V)❹<br />
A<br />
Short-time allowable current for 10s<br />
(IEC/EN 60947-1)<br />
A<br />
BF9C BF12C BF16C BF20C BF25C BF32C BF40C❶ BF40C 40❷<br />
3-4 3 3-4 3 3-4 3 3 4<br />
690<br />
8<br />
25-400❸<br />
25 25 25 40 40 55 60 60<br />
9 12 16 20 25 32 40 40<br />
5.3 7.2 7.5 10 11.7 16 20 20<br />
110 110 130 160 200 320 320 320<br />
Max fuse size SC/gG A 32 40 40 50 50 63 80 80<br />
Type 1 or 2 aM A 10 12 16 20 25 32 40 40<br />
Making capacity (RMS value) A<br />
210 210 210 350 350 480 480 480<br />
Breaking capacity ≤440V A 210 210 210 350 350 480 480 480<br />
at voltage<br />
500V A 160 160 160 290 290 320 320 320<br />
690V A 120 120 120 220 220 270 270 270<br />
Consumption and<br />
mΩ 5 5 5 2.5 2.5 2.0 1.8 1.8<br />
resistance per pole<br />
Ith W 3.1 3.1 3.1 4.0 4.0 6.0 6.5 6.5<br />
(average values)<br />
AC3 W 0.40 0.72 1.3 1.0 1.6 2.0 2.6 2.6<br />
Terminals in. (mm)<br />
Type<br />
Clamp-screw<br />
A<br />
0.32 (8.3) 0.4 (10.1) 0.52 (13.2)<br />
B<br />
0.14 (3.5) 0.23 (5.9) 0.22 (5.5)<br />
A<br />
Screw M3.5 M3.5 M3.5 M4 M4 M5 M5 M5<br />
Phillips 2 2 2 2 2 2 2 2<br />
Min-Max tightening torque<br />
Nm 1.4-1.8 1.4-1.8 1.4-1.8 1.8-2.3 1.8-2.3 3.1-3.9 3.1-3.9 3.1-3.9<br />
for contact terminal<br />
Ibft 1.03-1.33 1.03-1.33 1.03-1.33 1.32-1.70 1.32-1.70 2.24-2.88 2.24-2.88 2.24-2.88<br />
Min-Max tightening torque<br />
Nm 0.8-1 0.8-1 0.8-1 0.8-1 0.8-1 0.8-1 0.8-1 0.8-1<br />
for coil terminals<br />
lbft 0.59-0.74 0.59-0.74 0.59-0.74 0.59-0.74 0.59-0.74 0.59-0.74 0.59-0.74 0.59-0.74<br />
Phillips 2 2 2 2 2 1 1 1<br />
Maximum conductor section<br />
connectable with 1 or 2 wires<br />
AWG n° 10 10 10 8 8 4 4 4<br />
Flexible w/o lug<br />
(min-max) mm 2 1-6 1-6 1-6 1.5-10 1.5-10 2.5-16 2.5-16 2.5-16<br />
Flexible c/w lug mm 2 6 6 6 6 6 6 6 6<br />
Power terminal protection<br />
according to EN 60529<br />
IP20❺ IP20❺ IP20❺ IP20❻ IP20❻ IP20❼ IP20❼ ––<br />
AMBIENT CONDITIONS<br />
Operating temperature<br />
Storage temperature<br />
Maximum altitude<br />
°F<br />
°F<br />
ft<br />
-60 to +160 (-50 to +70°C)<br />
-75 to +175 (-60 to +80°C)<br />
9800 (3000m)<br />
Operating<br />
position<br />
Fixing<br />
Normal<br />
Allowable<br />
On vertical plane<br />
± 30°<br />
Screw or 35mm DIN rail (IEC/EN 60715)<br />
❶ Three-pole version.<br />
❷ Four-pole version, 4NO type (main poles). For data of the 2NO+2NC type, contact Sales & Technical Support.<br />
❸ Derating for use at 61-400Hz. Contact Sales & Technical Support.<br />
❹ Current values guarantee an electrical life of about 200,000 cycles.<br />
❺ IP20 protection warranted by wired equipment; minimum 18 AWG / 1mm 2 conductor section.<br />
❻ 14 AWG / 2.5mm 2 conductor section for 3-pole type or 10 AWG / 6mm 2 for 4-pole type<br />
❼ IP20 protection warranted by wired equipment; minimum 6 AWG / 16mm 2 conductor section.<br />