If the required format is not shown or the format that you are using is not known<br />

try the configuration with Auto Wiegand or Auto Magnetic. If the data fails to<br />

decode contact <strong>Integrated</strong> Control Technology, we can attempt to create or find a<br />

format solution for the reading device you are using.<br />

Reader Port 1 Secondary Reading Format<br />

The secondary reading format is used to program an alternate format for the reader expander<br />

and has the same options as the standard reader selection. The secondary format will only be<br />

used if the first format can not decode the card information that is received by the reader<br />

interface.<br />

RD001 R1 Format<br />

None<br />

Use the [1] and [3] keys to scroll the available card reader format settings. For more<br />

information about the list control data entry refer to the section List Control Data Entry on<br />

Page 406.<br />

For a list of supported formats refer to the Reader Expander Format Table on Page<br />

94.<br />

Reader Port 1 Reader Type<br />

The reader type informs the reader expander which location of the door the reader is installed<br />

that is connected to the reader expander port one. The reader expander uses this information<br />

to pass the correct direction of travel to the door control functions. For an access door this<br />

should be set to ENTRY reader.<br />

When using the reader with a door that controls an inside or outside area for arming or<br />

disarmed or for global anti-passback the ENTRY and EXIT configuration must be set correctly<br />

to ensure the correct action is taken by the reader expander.<br />

RD001 R1 Type<br />

ENTRY Reader<br />

Use the [1] and [3] keys to scroll the available reader type settings. For more information<br />

about the list control data entry refer to the section List Control Data Entry on Page 406.<br />

Arming Mode<br />

ENTRY Reader<br />

EXIT Reader<br />

Operation<br />

The reader is located on the outside of the door and is used<br />

to enter in to the area that is being protected by the door.<br />

This is the default setting and should be set for all general<br />

access doors (single reader)<br />

The reader is located on the inside of the door and is used<br />

to exit out of the area that is being protected by the door.<br />

If the reader expander is configured for multiplex<br />

reader mode the multiplexed reader is ALWAYS the<br />

EXIT reader.<br />

Reader Port 1 Keypad Operation Mode<br />

The keypad operation mode programmed for the reader on port one determines if the reader<br />

port has a pin entry device attached or uses a local LCD keypad.<br />

97 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>