O The 2 Reader expander is online.<br />

('*' will indicate the expander is offline)<br />

To view the IP address of the module press the [] key from this view. If the module is<br />

connected over the RS-485 LAN “---.---.---.---“ will be displayed.<br />

To list all offline or online modules refer to the Module Network Functions on Page 265.<br />

Special functions are provided to update, update reset a module and request offline events<br />

from a module. In the case of a update or update reset this occurs for the individual module<br />

however pressing the memory key will start the event request process for the by using a<br />

shortcut key directly from the keypad selection screen.<br />

Key<br />

[STAY]<br />

[FORCE]<br />

[MEMORY]<br />

Function<br />

Pressing the [STAY] key will update the zone expander number that is<br />

currently displayed in the module selection window. This will program<br />

the module WITHOUT resetting the module.<br />

Pressing the [FORCE] key will update and init the zone expander<br />

number that is currently displayed in the module selection window. This<br />

will program the module and then restart the module.<br />

Pressing the [MEMORY] key will start the system controller in the<br />

offline event update mode. This forces the controller to request all<br />

offline events from the Intelligent or Ethernet Reader Expanders.<br />

Pressing the [MEMORY] key while the system controller is already<br />

updating the network or performing other functions the [MEMORY] key<br />

will not have any function.<br />

Module Polling Time<br />

The polling time defines how often the Reader Expander module checks in with the Protégé<br />

System <strong>Controller</strong>. If a Reader Expander fails to check in, it triggers its associated<br />

communication failure (RDxxx:16) trouble zone and the trouble zone for a general module<br />

communications failure.<br />

To enter a polling time (008 to 250 seconds), use the keypad as explained in section Entering<br />

Decimal Numbers on Page 405 and press [ENTER]. By default the Reader Expander polling<br />

time is set to 250 seconds. Setting a polling time below 60 seconds should only be done for<br />

Reader Expanders that are in a non-secure area.<br />

RD001 Polling<br />

time: 250 secs<br />

For UL and cUL listed installations you MUST set the polling time to 180 seconds or<br />

less.<br />

Reader Expander Module Options<br />

Options that relate to the reader expander module can be set using option entry.<br />

RD001 Module<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options on Page 409.<br />

Option 1 - High Current Charging<br />

91 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>