To enter a dual user entry time (001 to 250 seconds), use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER].<br />

Keypad Invalid Code Lockout Time<br />

If the Lockout option is enabled for the selected keypad and the maximum number of<br />

incorrect user codes (PIN Numbers) is reached (3 Times), the time programmed here defines<br />

how long the keypad will be locked out. During this period, the keypad will display the lockout<br />

message and ignore all key entries or login attempts by ay user. A lockout time of 0 seconds<br />

will disable this function regardless of the lockout option setting.<br />

KP001 Invalid<br />

time: 060 secs<br />

To enter a lockout time (001 to 250 seconds), use the keypad as explained in section Entering<br />

Decimal Numbers on Page 405.<br />

Keypad Smoke Detector Reset PGM<br />

The PGM that is programmed as the keypad smoke detector reset PGM will be activated when<br />

a user press's the [CLEAR + ENTER] keys together. The selected PGM should have a time<br />

programmed of 5 to 10 seconds, for information on setting a PGM activation time refer to the<br />

PGM Programming section on Page 146.<br />

KP001 Smoke<br />

pgm: -----:--<br />

To enter a smoke detector PGM, use the keypad as explained in section Entering PGM and<br />

PGM Groups on Page 410.<br />

Keypad Module Options<br />

Options that relate to the keypad module can be set using option entry.<br />

KP001 Module<br />

[1-34----]<br />

To modify options, use the keypad as explained in section Entering Data Options on Page 409.<br />

Option 1 - Beep on Key Press<br />

Enabled the keypad will NOT beep when a key is pressed.<br />

Disabled the keypad will generate a beep tone each time a key is pressed.<br />

Option 2 - Zone Duplex Operation<br />

Enabled the keypad will enable the Duplex Zone option making it possible to<br />

connect four zone inputs to the keypad.<br />

Disabled the keypad will use the standard zone configuration settings.<br />

Option 3 - Keypad Lockout<br />

79 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>