16 Burglary Alarm 06 (BA) 86 (BH)<br />

17 Perimeter Alarm 06 (BA) 86 (BH)<br />

18 Interior Alarm 06 (BA) 86 (BH)<br />

19 24 Hour Alarm 11 (UA) 91 (UH)<br />

20 Entry Exit Alarm 08 (BA) 88 (BH)<br />

21 Day Night Alarm 06 (BA) 86 (BH)<br />

22 Outdoor Alarm 06 (BA) 86 (BH)<br />

23 Tamper Alarm 17 (TA) 97 (TH)<br />

24 Near Alarm 06 (BA) 86 (BH)<br />

25 Combustion 06 (BA) 86 (BH)<br />

26 Gas Detected 0F (GA) 8F (GH)<br />

27 Freezer / Refrigeration 0E (ZA) 8E (ZH)<br />

28 Heat Loss 10 (KA) 90 (KH)<br />

29 Water Leakage 0D (WA) 8D (WH)<br />

30 Foil Broken 14 (UA) 94 (UH)<br />

31 Day Trouble Alarm 12 (UA) 92 (UH)<br />

CID (Contact ID)<br />

Contact ID is a DTMF reporting protocol that uses a 3 digit account code and 3 digit reporting<br />

codes for each alarm transmission type. It is also possible to assign a special code to the zone<br />

type being used for a specific group of zones if needed. The custom types are shown in the<br />

table following the zone types assigned to each module.<br />

Zones are reported using the standard burglary codes.<br />

Alarm / Open 130 (Burglary) (R For Restore)<br />

Tamper 137 (Burglary Tamper) (R For Restore)<br />

Bypass 570 (Zone Bypass) (R For Restore)<br />

Contact ID Message Format<br />

The format of the Contact ID message that is sent to the Monitoring Station receiver is static<br />

and does not change from the standard specified SIA DC-05-1999.09 reorder code 14085.<br />

The message composition is in the following form:<br />

ACCT MT QXYZ GG CCC S<br />

Where:<br />

ACCT 4 Digit Account Number composed using the digits 0-9<br />

and B-F.<br />

MT<br />

Message Type. This two digit sequence is used to<br />

identify the Contact ID message to the receiver. It may<br />

be transmitted as 18 (preferred) or 98 (optional). The<br />

Protégé System <strong>Controller</strong> ONLY transmits the 18<br />

identifier.<br />

Q<br />

Event Qualifier<br />

1 = New Event or Opening<br />

3 = New Restore or Closing<br />

6 = Previously reported condition still present (Status<br />

Report)<br />

XYZ<br />

3 Digit Event Code composed using the digits 0-9 and<br />

B-F.<br />

385 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>