Keypad Zones<br />

The keypad will report trouble zones from 1 to 8 on the first 2 modules, all modules above<br />

address KP002 will be reported using the default code of 999.<br />

Zone Number Contact ID Code Reporting Point Number<br />

KP001:01 145 (Module Tamper) 565<br />

KP001:02 302 (Low Voltage) 566<br />

KP001:03 120 (Panic 1+3) 567<br />

KP001:04 121 (Duress Code) 568<br />

KP001:05 423 (Forced Access) 569<br />

KP001:06 426 (Door Open) 570<br />

KP001:07 461 (Invalid Code Lockout) 571<br />

KP001:08 143 (Module Offline) 572<br />

KP002:01 145 (Module Tamper) 573<br />

KP002:02 302 (Low Voltage) 574<br />

| | | | | | | |<br />

KP002:08 143 (Module Offline) 612<br />

KP003:01 145 (Module Tamper) 999<br />

| | | | | | | |<br />

KP250:04 143 (Module Offline) 999<br />

In the above table a reporting code of 999 indicates that the zone is outside the maximum<br />

zones that can be reported for the module type.<br />

16 Zone Expander<br />

The 16 zone expander will report trouble zones from 1 to 16 on the first 20 modules, all<br />

modules above address ZX020 will be reported using the default code of 999.<br />

Zone Number Contact ID Code Reporting Point Number<br />

ZX001:01 145 (Module Tamper) 613<br />

ZX001:02 301 (AC Loss) 614<br />

ZX001:03 302 (Low System Battery) 615<br />

ZX001:04 312 (Auxiliary Fuse) 616<br />

ZX001:05 321 (Siren/Bell 1 Tamper) 617<br />

ZX001:06 322 (Siren/Bell 2 Tamper) 618<br />

ZX001:07 312 (Siren/Bell 1 Over Current) 619<br />

ZX001:08 312 (Siren/Bell 2 Over Current) 620<br />

ZX001:09 140 (General Alarm) 621<br />

ZX001:10 140 (General Alarm) 622<br />

ZX001:11 140 (General Alarm) 623<br />

ZX001:12 140 (General Alarm) 624<br />

ZX001:13 140 (General Alarm) 625<br />

ZX001:14 140 (General Alarm) 626<br />

ZX001:15 140 (General Alarm) 627<br />

ZX001:16 143 (Module Offline) 628<br />

ZX002:01 143 (Module Tamper) 629<br />

| | | | | | | |<br />

ZX020:16 143 (Module Offline) 676<br />

ZX021:01 145 (Module Tamper) 999<br />

| | | | | | | |<br />

ZX250:16 143 (Module Offline) 999<br />

In the above table a reporting code of 999 indicates that the trouble zone is outside the<br />

maximum trouble zones that can be reported for the module type.<br />