Zone Number Contact ID Code Reporting Point Number<br />

RD001:01 130 (Burglary) 105<br />

RD001:02 130 (Burglary) 106<br />

RD001:03 130 (Burglary) 107<br />

RD001:04 130 (Burglary) 108<br />

RD001:05 130 (Burglary) 109<br />

RD001:06 130 (Burglary) 110<br />

RD001:07 130 (Burglary) 111<br />

RD001:08 130 (Burglary) 112<br />

RD002:01 130 (Burglary) 113<br />

| | | | | | | |<br />

RD016:08 130 (Burglary) 232<br />

RD017:01 130 (Burglary) 999<br />

| | | | | | | |<br />

RD250:08 130 (Burglary) 999<br />

In the above table a reporting code of 999 indicates that the zone is outside the maximum<br />

zones that can be reported for the module type.<br />

16 PGM Output Expander<br />

The 16 PGM Output expander will not report any zones as no physical connection is provided<br />

on the 16 PGM output expander. Trouble zones will be reported please see following section.<br />

Analog Input/Output Expander<br />

The Analog Input and Output Expanders will not report any zones as no physical connection is<br />

provided on the Analog Input and Output expanders. Trouble zones will be reported, refer to<br />

the trouble zone section.<br />

Contact ID Standard Trouble Zones<br />

The following tables show the reporting codes for the trouble zones when the Contact ID<br />

Standard Table is used (Table 000, Default).<br />

Control Panel Trouble Zones<br />

The control panel will report all trouble zones from 1 to 64 using any of the available table<br />

configurations.<br />

Zone Number Contact ID Code Reporting Point Number<br />

CP001:01 145 (Module Tamper) 501<br />

CP001:02 301 (AC Loss) 502<br />

CP001:03 302 (Low System Battery) 503<br />

CP001:04 626 (RTC Inaccurate) 504<br />

CP001:05 602 (Periodic Test Report) 505<br />

CP001:06 354 (Fail To Communicate) 506<br />

CP001:07 351 (Phone Line TLM Fail) 507<br />

CP001:08 312 (Auxiliary Fuse) 508<br />

CP001:09 145 (Bell/Siren 1 Tamper) 509<br />

CP001:10 145 (Bell/Siren 2 Tamper) 510<br />

CP001:11 321 (Bell/Siren 1 Over Current) 511<br />

CP001:12 322 (Bell/Siren 2 Over Current) 512<br />

CP001:13 143 (Module Lost) 513<br />

CP001:14 143 (Module Security) 514<br />