that a service that uses the setting is restarted (for example changing the TCP/IP Address<br />

requires that the TCP/IP service is restarted).<br />

AC Failure Time<br />

The AC Failure time allows the installer to program a time that AC mains voltage must have<br />

failed before activating the AC Failure Trouble Zone. Set this to a larger value for locations<br />

that experience frequent but short interruptions in power or that operates on a generator<br />

frequently.<br />

AC Failure<br />

time: 030 secs<br />

To modify the AC Failure time (000 to 255 Seconds), use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER].<br />

AC Restore Time<br />

The AC Restore time allows the installer to program a time that AC must be present for after<br />

a AC Failure before restoring the AC Failure Trouble Zone. Set this to a larger value for<br />

locations that experience frequent but short interruptions in power or that operates on a<br />

generator frequently.<br />

AC Restore<br />

time: 030 secs<br />

To modify the AC Restore time (000 to 255 Seconds), use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER].<br />

Battery Test Time<br />

The battery test time allows the installer to program the duration of time in minutes between<br />

each battery test that is performed. A battery test is performed immediately on power up of<br />

the panel and then every programmed period. Each battery test takes 45 seconds and the<br />

battery low/failure trouble zone will activate if the battery fails.<br />

Battery Test<br />

Time: 015 mins<br />

To modify the Battery Test time (000 to 255 Minutes), use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER].<br />

Default LCD Text Line One<br />

The default LCD text for line one is shown on all <strong>PRT</strong>-KLCD keypads when they are first<br />

connected to the system. This text should be changed to the name of the building, installation<br />

or owners details. To view the information on setting the time, date or other variable text see<br />

the formatting character information in the following section.<br />

Def LCD Line 1<br />

Protege System<br />

To modify or enter a new name for the selected default LCD line item use the keypad as<br />

explained in section Entering Text and Names on Page 406 and press [ENTER].<br />