Base Register Configuration<br />

Register 00100 Input Set Point = 1200<br />

Register 00101 Input Hysterisis = 100<br />

Register 00102 Input Hysterisis Time = 20<br />

Given the above settings and assuming that the data value for the input comparison is set to<br />

0 when the programmable function is started after 20 seconds the low PGM (if it is set) will be<br />

activated. When the data value rises and exceeds the 1200 set point for longer than 20<br />

seconds (Hysterisis Time) the low value will be deactivated. If the input then exceeds the set<br />

point plus the hysterisis value (1300) for longer than 20 seconds the high PGM will be<br />

activated and will deactivate when the input value is below the set point for longer than the<br />

20 second time.<br />

Setting a very low hysterisis time value can result in the system oscillating and causing<br />

unstable operation, it is recommended to have a reasonable value for these settings.<br />

Daylight Sensor<br />

For example a daylight sensor that can be used would be set to hysterisis of 250 and a time<br />

of 120 seconds, this ensures any variation in cloud cover, headlights or other scenarios are<br />

managed by the comparison function and would not cause the lights being controlled from<br />

either flicking off or on in a brief over/under light situation.<br />

Comparison Input Register<br />

The comparison input register is used for the source of the data to perform a comparison. For<br />

example using a register setting of 00000 would perform a comparison with the data being<br />

sent from Channel 1 of the first Analog Expander.<br />

The comparison input register DOES NOT have to be a register that is linked with an<br />

analog expander. This can be a register that is controlled from the Protégé System<br />

Management suite or from another register. This is also an ideal method of testing<br />

the comparison function before putting it in to operation.<br />

FN001 Comp inp<br />

reg: 00000<br />

To modify the comparison input register (00000 to 65535), use the keypad as explained in<br />

section Entering Decimal Numbers on Page 405 and press [ENTER].<br />

Ripple Control PGM Output Function<br />

The ripple control function will activate and then deactivate in sequence the PGM's that are<br />

assigned to the stage outputs. Ideally suited for staging on lighting and air conditioning<br />

systems in large industrial sites.<br />

FN001 Func Type<br />

Ripple PGM<br />

Use the [1] and [3] keys to scroll the function types until you reach the Ripple PGM selection<br />

and press [ENTER] to select the function type displayed and proceed to the next<br />

programmable option for the Value Compare function. For more information about the list<br />

control data entry refer to the section List Control Data Entry on Page 406.<br />