duration of the hysterisis time. The low PGM will turn off if the input value is above the set<br />

point value.<br />

FN001 Low<br />

pgm: --000:00<br />

To modify the low PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410.<br />

Base Data Register<br />

The Base data register is used as the first register in the list of registers used to configure,<br />

program and control the Value Compare. The only registers that are not included in the base<br />

registers are ones that must link to an analog input or analog output for external sensors<br />

(Temp, Daylight (LUX), Water Level). A base data register setting MUST be set to ensure the<br />

system can pick up the set points and data values.<br />

FN001 Base data<br />

reg: 00000<br />

To modify the base data register (00000 to 65535, use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER].<br />

Base Data Register Offset<br />

Register Offset Register Function<br />

0 Input Value Set Point<br />

The input value set point is used to determine at what point the<br />

comparison input register value used in the calculation is high or<br />

low. The Input Hysterisis value is added or subtracted from the set<br />

point to prevent an oscillation on the output PGM's.<br />

1 Input Hysterisis Value<br />

The hysterisis value that the comparison input must be above or<br />

below the setpoint to activate the low or high PGM outputs. This<br />

value is added to the input value or subtracted dependent on the<br />

direction the comparison input is changing.<br />

2 Input Hysterisis Time<br />

The time that the value must be above or below the set point to<br />

proceed with activating the low and high PGM outputs. This setting<br />

is the number of seconds the value must be above or below.<br />

Using the register configuration settings above and the following data values in the<br />

configuration registers the following will be observed. The comparison input register in this<br />

example is linked to the first channel on the Analog Expander. This was tested using a linear<br />

variable resistor with a 10V supply reference that can be connected to the input to allow<br />

manual control using the knob on the variable resistor.<br />

Programmed Settings<br />

Base Register is 00100<br />

Value Data Register is 00000 (First Analog Input Channel on AE001)<br />