modes.<br />

4 Current Floor Tempering Mode<br />

The current mode that the floor tempering is operating in. The<br />

floor tempering modes are listed in the section below.<br />

Floor Tempering Mode Definition<br />

Register Offset Register Function<br />

0 Floor Tempering Idle Condition<br />

The programmable function is idle and no processing is taking<br />

place.<br />

1 Floor Tempering Waiting For Start Signal<br />

The programmable function is waiting for the enable PGM signal to<br />

be controlled to an ON state to start operation. This is usually<br />

managed by a schedule or the alarm status. When the signal is<br />

received the Fan PGM will be activated and the programmable<br />

function will enter a delay of 30 seconds before starting.<br />

2 Floor Tempering Waiting Check<br />

If the floor tempering is checking if it requires to operate in a<br />

manual or automatic mode.<br />

3 Floor Tempering Dead Band Process<br />

The dead band process is where the floor tempering will wait for a<br />

condition that is outside the set point for tempering of the floor or<br />

heating the duct.<br />

4 Floor Heating<br />

The floor temperature is below the floor heating set point and the<br />

function to start the heating process is active. This will activate the<br />

floor heater that is required to bring the temperature up to the<br />

heating set point.<br />

5 Floor Cooling<br />

The floor temperature is above the floor heating set point and the<br />

function to start the cooling process is active. This will operate the<br />

floor tempering in reverse and disable the duct heater.<br />

6 <strong>Manual</strong> Heating Forward<br />

The manual forward (heating) override PGM is active and the floor<br />

tempering is operating in <strong>Manual</strong> Heating mode.<br />

7 <strong>Manual</strong> Cooling Reverse<br />

The manual reverse (cooling) override PGM is active and the floor<br />

tempering is operating in <strong>Manual</strong> Cooling mode.<br />

8 RTHP Shutting Down<br />

The floor tempering is completing an orderly shutdown of the<br />

currently activated outputs and the fan control signal.<br />

9 Fault Condition<br />

A fault condition has activated that has caused the floor tempering<br />

to shut down. This condition is typical of a smoke damper closing<br />

Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong><br />

298