FN001 Cool on<br />

pgm: --000:00<br />

To modify the cool on PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410.<br />

Heat On PGM<br />

The heat on PGM is activated when the floor tempering has a requirement for heating and is<br />

activated only in the forward direction.<br />

FN001 Heat on<br />

pgm: --000:00<br />

To modify the heat on PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410.<br />

Base Data Register<br />

The Base data register is used as the first register in the list of registers used to configure,<br />

program and control the Floor Tempering system. The only registers that are not included in<br />

the base registers are ones that must link to an analog input or analog output for external<br />

sensors (Temp, Humidity or Dampers). A base data register setting MUST be set.<br />

FN001 Base data<br />

reg: 00000<br />

To modify the base data register (00000 to 65535, use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER].<br />

Base Data Register Offset<br />

Register Offset Register Function<br />

0 Tempering Set Point<br />

The tempering set point determines the temperature that the floor<br />

tempering will operate at. This value is compared with the floor<br />

temperature input to determine if cooling or heating is required<br />

and the direction of the fan.<br />

1 Floor Temperature Hysterisis Setting<br />

The floor temperature hysterisis value is subtracted from the floor<br />

temperature set point to allow the floor tempering to drive slightly<br />

above and below the set point.<br />

2 Duct Temperature Set Point<br />

This sets the maximum value for the duct sensor and is used to<br />

control the heating of the duct air.<br />

3 Duct Temperature Hysterisis Setting<br />

The duct temperature heating hysterisis value is added to the duct<br />

heating set point to allow the floor tempering to drive slightly<br />

beyond the set point. This setting prevents the floor tempering<br />

system from oscillating between the dead band and heating<br />

297 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>