Enabled Control PGM<br />

Enabled Control PGM is set when the Floor Temping is to run and will operate only when the<br />

enabled PGM is on. If no enabled PGM is set the Floor Temping will run continuously.<br />

Programming a PGM that is activated by a schedule allows the floor temping to operate only<br />

during the times that the space is occupied.<br />

FN001 Enabled<br />

pgm: --000:00<br />

To modify the enable PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410.<br />

Fault PGM<br />

The fault control PGM is set when a fault condition has occurred and the Floor Temping is to<br />

shutdown. This allows the Floor Temping to shutdown in the shortest possible time without<br />

causing any damage to the system. In the case of a fire shutdown the system must have a<br />

fire PGM programmed.<br />

FN001 Fault<br />

pgm: --000:00<br />

To modify the fault PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410.<br />

Fire PGM<br />

The fire control PGM is monitored NOT controlled by the function and when the fire PGM has<br />

been activated, typically by an external fire alarm input, the floor tempering will gracefully<br />

shut down the system and halt operation until the fire alarm has been cleared. This PGM<br />

could be the PGM used to deactivate smoke dampers and other related equipment in the<br />

HVAC control system.<br />

FN001 Fire<br />

pgm: --000:00<br />

To modify the fire PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410. Do not set a PGM group for the fire or other monitored PGM's as this will<br />

have no action in the control system and will be the same as not setting a PGM value.<br />

Fan Control PGM<br />

The fan PGM is activated when the floor tempering starts to operate and is started 30 seconds<br />

prior to any heating or cooling. The direction of the fan (forward and reverse) is determined<br />

by the forward and reverse PGM outputs. If a fan on signal is not required use the forward<br />

and reverse PGM outputs to drive the appropriate contactors.<br />

FN001 Fan<br />

pgm: --000:00<br />

To modify the fan PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups on Page 410.<br />

295 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>