Dehumidification stages are deactivated because the humidity has<br />

reached set point and dehumidification is no longer required.<br />

16 RTHP Shutting Down<br />

The RTHP is completing an orderly shutdown of the currently<br />

activated stages and the fan control signals.<br />

17 Fault Condition<br />

A fault condition has activated that has caused the RTHP to shut<br />

down. This condition is typical of a smoke damper closing or other<br />

mechanical input that will result in the RTHP shutting down.<br />

18 Fire Condition<br />

A fire alarm condition has been activated that has caused the RTHP<br />

to shut down.<br />

Space Temperature Register<br />

The space temperature register is the register that is updated by an analogue module input<br />

channel connected to a temperature sensor. The space temperature is typically from a sensor<br />

located within the space the RTHP is controlling.<br />

FN001 Space temp<br />

reg: 00000<br />

To modify the space temperature register (00000 to 65535, use the keypad as explained in<br />

section Entering Decimal Numbers on Page 405 and press [ENTER].<br />

If you are unsure how the RTHP operates and what action is going to be started as a<br />

result in the change in the input registers you can specify the register to be a<br />

normal register outside the analogue module range. This will allow an installer to<br />

modify the values with the Protégé System Management Suite and visually see the<br />

mode change in the RTHP without the need to physically connect the RTHP.<br />

Space Humidity Register<br />

The space humidity register is the register that is updated by an analogue module input<br />

channel connected to a humidity sensor. The space humidity sensor is typically located within<br />

the space the RTHP is controlling at a height of 1.5 to 2.5 meters above floor level.<br />

FN001 Space rh<br />

reg: 00000<br />

To modify the space humidity register (00000 to 65535, use the keypad as explained in<br />

section Entering Decimal Numbers on Page 405 and press [ENTER].<br />

External Fresh Air Temperature Register<br />

The external fresh air temperature register is the register that is updated by an analogue<br />

module input channel connected to a temperature sensor. The external fresh air temperature<br />

is typically from a sensor located within fresh air intake of the RTHP in the cowling section.<br />

The fresh air temperature sensor is used to calculate the ability to cool the space with direct<br />

fresh air and is calculated prior to a demand for cooling.<br />

293 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>