dehumidification.<br />

5 On Call For Space Heating<br />

The space temperature is below the heating set point and the<br />

function to start the heating process is active. This will activate the<br />

stages required to bring the temperature up to the heating set<br />

point.<br />

6 On Call For Space Cooling<br />

The space temperature is above the cooling set point and the<br />

function to start the cooling process is active. This will activate the<br />

stages required to bring the temperature down to the cooling set<br />

point.<br />

7 On Call For Fresh Air Space Cooling<br />

The space temperature is above the cooling set point and the<br />

outside air is below the free air cooling set point, the RTHP will<br />

oscillate the fresh air economizer in attempt to cool the space<br />

using the fresh air intake. This will remain active until the<br />

temperature is below the cooling set point or if the free cooling<br />

fails to achieve set point in the set time (Free Cooling Time) mode<br />

6 will be entered.<br />

8 Heating Stage Off<br />

Heating stages are being turned off progressively due to the set<br />

point being reached.<br />

9 Cooling Stage Off<br />

Cooling stages are being turned off progressively due to the set<br />

point being reached.<br />

10 Dehumidification Cooling Plus Reheat<br />

Dehumidification is required and the current set point is above the<br />

cooling set point. The dehumidification stage will be entered in an<br />

attempt to get the humidity under control.<br />

11 Dehumidification Transition<br />

The dehumidification process is in a transition between the<br />

dehumidification requirements and cooling.<br />

12 Dehumidification Heating<br />

Dehumidification is required and the current set point is below the<br />

heating set point. The dehumidification stage will be entered in an<br />

attempt to get the humidity under control while an attempt is also<br />

made to obtain heating set point.<br />

13 Dehumidification Heating Stage Off<br />

Dehumidification and heating stages are deactivated because the<br />

humidity has come under control or the cooling set point (other<br />

side of the dead band setting) has been reached.<br />

14 Dehumidification Cooling Stage Off<br />

Dehumidification and cooling stages are deactivated because the<br />

humidity has come under control or the heating set point (other<br />

side of the dead band setting) has been reached.<br />

15 Dehumidification Stage Off<br />

Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong><br />

292