The integral gain is the gain of the integral portion of the PI loop<br />

and is a division of the actual integral error amount that is used to<br />

form the calculation. The integral gain will divide by 1, 2, 4, 8 etc<br />

by setting a value of 1,2,3,4 ... 15.<br />

If a value of 0 is programmed for the integral gain<br />

the system will not use integral within the PI loop<br />

and it will be disabled.<br />

18 Integral Maximum Value<br />

As the integral value is a calculated value that is continually<br />

updated it can easily reach a saturation point where the plant can<br />

not meet the integral and plant error values. In this case we<br />

program a limit that will stop the integral from increasing beyond a<br />

recoverable point.<br />

19 Integral Calculation Time<br />

The integral calculation time is a time base used by the integral<br />

portion of the PI loop to update the Integral Error. It is advised not<br />

to set this below a value of 30 seconds.<br />

20 Fresh Air Damper Normal Setting<br />

The fresh air damper normal setting is the value that is output on<br />

the fresh air economiser analogue output used to control the fresh<br />

air damper position. This value allows the system to be tuned to<br />

an appropriate setting to allow the require Litres Per Second of<br />

fresh air to enter the RTHP.<br />

Roof Top Heat Pack Mode Definition<br />

Register Offset Register Function<br />

0 RTHP Idle Condition<br />

The programmable function is idle and no processing is taking<br />

place.<br />

1 RTHP Waiting For Start Signal<br />

The programmable function is waiting for the enable PGM signal to<br />

be controlled to an ON state to start operation. This is usually<br />

managed by a schedule or the alarm status. When the signal is<br />

received the Fan PGM will be activated and the programmable<br />

function will enter a delay of 30 seconds before starting.<br />

2 RTHP Warm Up Check<br />

If the RTHP is programmed to enter a warm up state at the start of<br />

operation the temperature will be checked here to verify if the<br />

warm up temperature is above the current space temperature if it<br />

is then the RTHP will enter the warm up mode.<br />

3 RTHP Warm Up Space<br />

When in warm up mode the RTHP is driven to full capacity to get<br />

the space above the heating set point in the fastest possible time.<br />

Once the temperature reaches this level the system will operate<br />

normally.<br />

4 RTHP Deadband Process<br />

The deadband process is where the RTHP will wait for a condition<br />

that is outside the set points for heating, cooling or<br />

291 Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong>