7 Fresh Air Cooling Set Point<br />

If the fresh air cooling set point is not 0 the system will check the<br />

fresh air temperature when a cooling demand exists and modulate<br />

the dampers to allow free cooling. The system will remain in the<br />

free cooling mode for the time set by the free cooling time.<br />

8 Stage 1 Demand Value<br />

The stage one demand value is the amount of plant error that is<br />

required to activate the first stage of cooling or heating. Plant error<br />

is calculated using a custom PI loop. The error is accumulated<br />

using the settings for the Integral Value and Hysterisis Settings.<br />

The error value is the difference between the set point and the<br />

current space temperature with the addition of the accumulated<br />

error.<br />

9 Stage 2 Demand Value<br />

The stage two demand value is the amount of plant error that is<br />

required to activate the second stage of cooling or heating.<br />

10 Stage 3 Demand Value<br />

The stage three demand value is the amount of plant error that is<br />

required to activate the third stage of cooling or heating.<br />

11 Stage 4 Demand Value<br />

The stage four demand value is the amount of plant error that is<br />

required to activate the fourth stage of cooling or heating.<br />

12 Current RTHP Mode<br />

The current mode that the RTHP is operating in. The RTHP modes<br />

are listed in the section below.<br />

13 Current Plant Error<br />

The current plant error is the error in the temperature value<br />

difference between the set point and the current temperature. This<br />

value is for display only and used to calculate the drive required<br />

for the RTHP to obtain the desired set point.<br />

14 Integral Error<br />

The integral error is the amount of raw calculated error using the<br />

integral portion of the PI loop used for the control of the RTHP unit<br />

and is calculated ONLY in a cooling or heating requirement mode.<br />

15 Integral Term<br />

The integral term is the result of a calculation using the integral<br />

gain and the integral error to obtain a value that can be used to<br />

add with the Plant Error to ensure that the heating and cooling set<br />

points are meet with the maximum amount of efficiency.<br />

16 Output Error<br />

The output error is the absolute output error at the current point<br />

and can be used as a guide when tuning the RTHP. The output<br />

error represents the Integral Term added with the raw Plant Error<br />

values. The output error is used to calculate the staging of the<br />

heating and cooling within the RTHP unit.<br />

17 Integral Gain<br />

Protégé <strong>Integrated</strong> System <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong><br />

290