FN001 Base data<br />

reg: 00000<br />

To modify the base data register (00000 to 65535, use the keypad as explained in section<br />

Entering Decimal Numbers on Page 405 and press [ENTER].<br />

Base Data Register Offset<br />

Register Offset Register Function<br />

0 Heating Set Point<br />

The heating set point determines the temperature that the RTHP<br />

will heat the space to and is compared with the temperature<br />

sensor connected to the Space Temp input.<br />

1 Cooling Set Point<br />

The cooling set point determines the temperature that the RTHP<br />

will cool the space to and is compared with the temperature sensor<br />

connected to the Space Temp input.<br />

2 Relative Humidity Set Point<br />

The relative humidity set point determines at what humidity level<br />

the RTHP will go in to a dehumidification cycle and drive the plant<br />

to reduce this amount. The relative humidity set point when<br />

exceeded is added or subtracted using the Hystersis value to<br />

prevent osciallation of the hyumidty modes.<br />

3 Heating Hysterisis Setting<br />

The heating hysterisis value is added to the heating set point to<br />

allow the plant to drive slightly beyond the set point. This allows<br />

specific heating and cooling tuning. Setting a value of 0 is not<br />

recommended as it can cause the system to oscillate between the<br />

dead band the heating modes.<br />

4 Cooling Hysterisis Setting<br />

The cooling hysterisis value is subtracted from the cooling set<br />

point to allow the plant to drive slightly below the set point. This<br />

allows specific heating and cooling tuning. Setting a value of 0 is<br />

not recommended as it can cause the system to oscillate between<br />

the dead band the cooling modes.<br />

5 Relative Humidity Hysterisis Setting<br />

The relative humidity hysterisis value is subtracted or added<br />

depending if the set point has already been exceeded to the<br />

relative humidity set point. This allows the relative humidity cycles<br />

to be tuned. Setting a value of 0 is not recommended as it can<br />

cause the system to oscillate between the relative humidity states.<br />

6 Warm Up Set Point<br />

If the warm up set point is not equal to 0 the system will check the<br />

space temperature against the warm up set point when the<br />

occupied relay is activated. If the internal temp is below the warm<br />

up set point the system will close the fresh air damper and drive<br />

the heating to achieve the heating set point. Once set point is<br />

reached the unit will operate in a normal mode.<br />